Status parameters

Code

 

Description

 

 

 

 

 

 

LRS6

Parameter name:

Extended status word 6

 

 

 

 

 

 

 

 

 

Logic address:

3255 = 16#0CB7

 

Type:

WORD (bit register)

 

CANopen index:

2002/38

 

Read/write:

R

 

INTERBUS index:

5FB9/23

 

 

 

 

DeviceNet path:

71/01/38

 

 

 

 

 

 

 

 

 

 

bit 0: = 1: Alarm group 1 is active

 

 

 

bit 1: = 1: Alarm group 2 is active

 

 

 

bit 2: = 1: Alarm group 3 is active

 

 

 

bit 3: = 1: Probe 1 alarm: [PTC1 alarm] (PtC1)

 

 

 

bit 4: = 1: Probe 2 alarm: [PTC2 alarm] (PtC2)

 

 

 

bit 5: = 1: LI6 PTC probe alarm: [LI6=PTC alarm] (PtC3)

 

 

 

bit 6: Reserved

 

 

 

 

 

bit 7: = 1: External fault [External fault alarm] (EtF)

 

 

 

bit 8: = 1: Undervoltage alarm [Undervoltage] (USA)

 

 

 

bit 9: = 1: The power section line supply loss detection threshold for a controlled stop has been reached (undervoltage

 

warning)

 

 

 

 

 

bit 10: Reserved

 

 

 

 

 

bit 11: = 1: Drive overheat alarm (tHA)

 

 

 

bit 12: Reserved

 

 

 

 

 

bit 13: Reserved

 

 

 

 

 

bit 14: Reserved

 

 

 

 

 

bit 15: = 1: Current or torque limit alarm after time-out [Trq/I limit. time out] (StO)

 

 

 

 

 

 

LRS7

Parameter name:

Extended status word 7

 

 

 

 

 

 

 

 

 

Logic address:

3256 = 16#0CB8

 

Type:

WORD (bit register)

 

CANopen index:

2002/39

 

Read/write:

R

 

INTERBUS index:

5FB9/24

 

 

 

 

DeviceNet path:

71/01/39

 

 

 

 

 

 

 

 

 

bit 0: = 1: Reference channel 1 (Fr1) or 1B (Fr1b) is active

 

 

bit 1: = 1: Reference channel 2 (Fr2) is active

 

 

 

bit 2: = 1: Command channel 1 (Cd1) is active

 

 

 

bit 3: = 1: Command channel 2 (Cd2) is active

 

 

 

bit 4: = 1: Reference channel 1B (Fr1b) is active

 

 

 

bit 5: Reserved

 

 

 

 

 

bit 6: Reserved

 

 

 

 

 

bit 7: Reserved

 

 

 

 

 

bit 8: = 1: IGBT thermal state alarm

 

 

 

bit 9: = 1: Braking resistor overload alarm

 

 

 

bit 10: = 1: Alarm sent by the "Controller Inside" card

 

 

 

bit 11: = 1: 4-20 mA alarm on analog input AI3: [AI3 4-20mA loss] (LFF3)

 

 

bit 12: = 1: 4-20 mA alarm on analog input AI4: [AI4 4-20mA loss] (LFF4)

 

 

bit 13: = 1: DC bus precharging contactor controlled (DC0)

 

 

 

bit 14: = 1: Flow limitation function active

 

 

 

bit 15: Reserved (= 0)

 

 

 

 

 

 

 

 

 

 

84

Page 84
Image 84
Schneider Electric 61 user manual LRS6, LRS7