Parameter set switching

The parameter set switching function (see the Programming Manual) can be used via the network or via the terminals.

To use this function via a network, simply assign one or two bits of the control word to parameter set switching via the [2 Parameter sets] (CHA1) and [3 Parameter sets] (CHA2) parameters.

The active set can be read in the "Active parameter set" (CFPS) parameter.

The parameter sets can be written via a network.

The parameter sets can be switched with the motor running.

Function parameters

Code

 

Description

 

 

 

 

 

 

 

 

 

 

 

 

CHA1

Parameter name:

Assignment for 2 sets

 

 

 

 

 

 

 

Terminal display:

[2 Parameter sets]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Logic address:

12902 = 16#3266

Type:

WORD (listing)

 

 

CANopen index:

2063/3

Read/write:

R/WS

 

 

 

INTERBUS index:

5FBD/3A

Factory setting:

0

 

 

 

DeviceNet path:

A1/01/67

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See next page.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHA2

Parameter name:

Assignment for 3 sets

 

 

 

 

 

 

 

Terminal display:

[3 Parameter sets]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Logic address:

12903 = 16#3267

Type:

WORD (listing)

 

 

CANopen index:

2063/4

Read/write:

R/WS

 

 

 

INTERBUS index:

5FBD/3B

Factory setting:

0

 

 

 

DeviceNet path:

A1/01/68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See next page.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFPS

Parameter name:

Active parameter set

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Logic address:

12900 = 16#3264

Type:

WORD (listing)

 

 

CANopen index:

2063/1

Read/write:

R

 

 

 

INTERBUS index:

5FB9/EB

 

 

 

 

 

 

 

DeviceNet path:

A1/01/65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0 = The parameter set switching function is not configured

 

 

 

 

1 = [Set 1 active] (CFP1): Parameter set no. 1 active

 

 

 

 

 

 

 

2 = [Set 2 active] (CFP2): Parameter set no. 2 active

 

 

 

 

 

 

 

3 = [Set 3 active] (CFP3): Parameter set no. 3 active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value of the control bit assigned by [2 Parameter sets] (CHA1)

 

0

 

1

0

1

 

 

 

 

 

 

 

Value of the control bit assigned by [3 Parameter sets] (CHA2)

 

0

 

0

1

1

 

 

 

 

 

 

 

 

Value of "Active parameter set" (CFPS)

 

 

1

 

2

3

3

 

 

 

 

 

 

 

 

Active parameter set

 

 

1

 

2

3

3

 

 

 

 

 

 

 

 

 

67

Page 67
Image 67
Schneider Electric 61 user manual Parameter set switching, CHA1, CHA2, Cfps