CiA402 profile
Stop commands:
The "Halt" command enables movement to be interrupted without having to leave the "5 - Operation enabled" state. The stop is performed in accordance with the [Type of stop] (Stt) parameter.
In the case of an
In the case of a
Regardless of the assignment of the [Type of stop] (Stt) parameter ([Fast stop] (FSt), [Ramp stop] (rMP), [Freewheel] (nSt), [DC injection] (dCI)), the drive remains in the "5 - Operation enabled" state.
A Fast Stop command at the terminals or using a bit of the control word assigned to Fast Stop causes a change to the "4 - Switched on" state. A "Halt" command does not cause this transition.
A Freewheel Stop command at the terminals or using a bit of the control word assigned to Freewheel Stop causes a change to the "2 - Switch on disabled" state.
WARNING
RISK OF EQUIPMENT DAMAGE
When the braking loop is configured, it is necessary to use the "Halt" command (bit 8 of CMD command word) to stop.
Failure to follow these instructions can result in death, serious injury or equipment damage.
Assigning control word bits
In the CiA402 profile, fixed assignment of a function input is possible using the following codes:
Bit | Integrated Modbus | CANopen | Network card | "Controller Inside" card |
|
|
|
|
|
bit 11 | C111 | C211 | C311 | C411 |
|
|
|
|
|
bit 12 | C112 | C212 | C312 | C412 |
|
|
|
|
|
bit 13 | C113 | C213 | C313 | C413 |
|
|
|
|
|
bit 14 | C114 | C214 | C314 | C414 |
|
|
|
|
|
bit 15 | C115 | C215 | C315 | C415 |
|
|
|
|
|
For example, to assign the DC injection braking to bit 13 of CANopen, simply configure the [DC injection assign.] (dCI) parameter with the [C213] (C213) value.
Bit 11 is assigned by default to the operating direction command [Reverse assign.] (rrS).
23