Schneider Electric 61 user manual Status parameters, Code, Description, Active command channel

Models: 61

1 131
Download 131 pages 6.3 Kb
Page 86
Image 86
Active command channel

Status parameters

Code

 

Description

 

 

 

 

 

 

CCC

Parameter name:

Active command channel

 

 

 

 

 

 

 

 

 

Logic address:

8442 = 16#20FA

 

Type:

WORD (bit register)

 

CANopen index:

2036/2B

 

Read/write:

R

 

INTERBUS index:

5FB9/D3

 

 

 

 

DeviceNet path:

8B/01/2B

 

 

 

 

 

 

 

 

 

 

bit 0: = 1: The terminals are the active command channel

 

 

 

bit 1: Reserved (= 0)

 

 

 

 

 

bit 2: = 1: The graphic display terminal is the active command channel

 

 

bit 3: = 1: Modbus is the active command channel

 

 

 

bit 4: Reserved (= 0)

 

 

 

 

 

bit 5: Reserved (= 0)

 

 

 

 

 

bit 6: = 1: CANopen is the active command channel

 

 

 

bit 7: = 1: The terminals are the active command channel in +/- speed

 

 

bit 8: = 1: The graphic display terminal is the active command channel in +/- speed

 

 

bit 10: = 1: The "Controller Inside" card is the active command channel

 

 

bit 11: Reserved (= 0)

 

 

 

 

 

bit 12: Reserved (= 0)

 

 

 

 

 

bit 13: Reserved (= 0)

 

 

 

 

 

bit 14: Reserved (= 0)

 

 

 

 

 

bit 15: = 1: The PowerSuite software workshop is the active command channel

 

 

 

 

 

 

CFPS

Parameter name:

Active parameter set

 

 

 

 

 

 

 

 

 

Logic address:

12900 = 16#3264

 

Type:

WORD (listing)

 

CANopen index:

2063/01

 

Read/write:

R

 

INTERBUS index:

5FB9/EB

 

 

 

 

DeviceNet path:

A1/01/65

 

 

 

 

 

 

 

 

 

 

0 : The parameter set switching function is not configured

 

 

 

1 = [Set 1 active] (CFP1): Parameter set no. 1 active

 

 

 

2 = [Set 2 active] (CFP2): Parameter set no. 2 active

 

 

 

3 = [Set 3 active] (CFP3): Parameter set no. 3 active

 

 

 

 

 

 

 

CNFS

Parameter name:

Active configuration

 

 

 

Terminal display:

[Config. Active]

 

 

 

 

 

 

 

 

 

Logic address:

8020 = 16#1F54

 

Type:

WORD (listing)

 

CANopen index:

2032/15

 

Read/write:

R

 

INTERBUS index:

5FB9/D1

 

 

 

 

DeviceNet path:

89/01/15

 

 

 

 

 

 

 

 

 

0 : The motor or configuration switching function is not configured

 

 

1 = (CNF0): Configuration no. 0 active

 

 

 

2 = (CNF1): Configuration no. 1 active

 

 

 

3 = (CNF2): Configuration no. 2 active

 

 

 

 

 

 

 

 

86

Page 86
Image 86
Schneider Electric 61 user manual Status parameters, Code, Description, Active command channel, Active parameter set