Schneider Electric 61 CiA402 standard configuration and adjustment parameters, Code, Description

Models: 61

1 131
Download 131 pages 6.3 Kb
Page 121
Image 121
Disable operation option code

CiA402 standard configuration and adjustment parameters

Code

 

Description

 

 

 

 

 

DOTD

Parameter name:

Disable operation option code

 

 

CiA402 name:

Disable operation option code

 

 

 

DRIVECOM name:

 

 

 

 

 

 

 

 

 

Logic address:

8652 = 16#21CC

Type:

WORD (listing)

 

CANopen index:

605C/0

Read/write:

R/WS

 

INTERBUS index:

5FBD/82

Factory setting:

0

 

DeviceNet path:

8C/01/35

 

 

 

 

 

 

 

 

Parameter conforming to CiA402 profile

 

 

 

0 = Freewheel stop

 

 

 

 

1 = Stop on ramp

 

 

 

 

 

 

 

 

QSTD

Parameter name:

Quick stop option code

 

 

 

CiA402 name:

Quick stop option code

 

 

 

DRIVECOM name:

 

 

 

 

 

 

 

 

 

Logic address:

8651 = 16#21CB

Type:

WORD (listing)

 

CANopen index:

605A/0

Read/write:

R/WS

 

INTERBUS index:

5FBD/81

Factory setting:

6

 

DeviceNet path:

8C/01/34

 

 

 

 

 

 

 

 

Parameter conforming to CiA402 profile

 

 

 

2 = Fast stop then transition to "2 - Switch on disabled" state

 

 

6 = Fast stop and remaining in "6 - Quick stop active" state

 

 

 

 

 

 

121

Page 121
Image 121
Schneider Electric 61 CiA402 standard configuration and adjustment parameters, Code, Description, Quick stop option code