I/O parameters

Code

 

 

Description

 

 

 

 

 

AI4C

Parameter name:

Physical image of analog input 4

 

 

 

 

 

 

 

 

Logic address:

5245 = 16#147D

 

Type:

INT

 

CANopen index:

2016/2E

 

Read/write:

R

 

INTERBUS index:

5FB9/39

 

Unit:

0.001 V or 0.001 mA

 

DeviceNet path:

7B/01/2E

 

 

 

 

 

 

 

 

 

 

The unit is:

 

 

 

 

 

• 0.001 V if parameter [AI4 Type] (AI4t) is configured as [Voltage] (10U)

 

 

• 0.001 mA if parameter [AI4 Type] (AI4t) is configured as [Current] (0A)

 

 

 

 

 

AI4r

Parameter name:

Standardized image of analog input 4

 

 

 

 

 

 

 

 

Logic address:

5235 = 16#1473

 

Type:

INT

 

CANopen index:

2016/24

 

Read/write:

R

 

INTERBUS index:

5FB9/35

 

Unit:

1

 

DeviceNet path:

7B/01/24

 

 

 

 

 

 

 

 

 

Analog outputs

The analog outputs can be controlled via the network. Simply write these parameters. The outputs to be controlled must not be assigned to a drive function, otherwise the write operation has no effect.

Code

 

Description

 

 

 

 

 

AO1C

Parameter name:

Physical image of analog output 1

 

 

 

 

 

 

 

Logic address:

5271 = 16#1497

Type:

INT

 

CANopen index:

2016/48

Read/write:

R/W

 

INTERBUS index:

5FB9/40 (reading via PCP)

Unit:

0.001 mA or 0.001 V

 

 

5FB6/50 (writing via PCP)

 

 

 

DeviceNet path:

7B/01/48

 

 

 

 

 

 

 

 

The unit is:

 

 

 

 

• 0.001 V if parameter [AO1 Type] (AO1t) is configured as [Voltage] (10U)

 

 

• 0.001 mA if parameter [AO1 Type] (AO1t) is configured as [Current] (0A)

 

 

 

 

 

AO1r

Parameter name:

Standardized image of analog output 1

 

 

 

 

 

 

 

Logic address:

5261 = 16#148D

Type:

INT

 

CANopen index:

2016/3E

Read/write:

R/W

 

INTERBUS index:

5FB9/3D (reading via PCP)

Unit:

1

 

 

5FB6/4F (writing via PCP)

 

 

 

DeviceNet path:

7B/01/3E

 

 

 

 

 

 

 

AO2C

Parameter name:

Physical image of analog output 2

 

 

 

 

 

 

 

Logic address:

5272 = 16#1498

Type:

INT

 

CANopen index:

2016/49

Read/write:

R/W

 

INTERBUS index:

5FB9/41 (reading via PCP)

Unit:

0.001 mA or 0.001 V

 

 

5FB6/52 (writing via PCP)

 

 

 

DeviceNet path:

7B/01/49

 

 

 

 

 

 

 

 

The unit is:

 

 

 

 

• 0.001 V if parameter [AO2 Type] (AO2t) is configured as [Voltage] (10U) or [Voltage +/-](n10U)

 

• 0.001 mA if parameter [AO2 Type] (AO2t) is configured as [Current] (0A)

 

 

 

 

 

 

 

 

 

 

 

98

 

 

 

 

Page 98
Image 98
Schneider Electric 61 user manual Analog outputs, AI4C, AO1C, AO2C