Forced local mode

Definition

Forced local mode supports switching to the terminals or display terminal.

This function complements channel switching and makes it possible to make use of an existing function from the Altivar 58 range.

Forced local mode is only available in CiA402 profile, not in I/O profile.

All other communication takes priority over forced local mode.

Forced local mode can be configured via the display terminal:

Menu

 

Submenu

 

 

 

[1.9 COMMUNICATION] (COM-)

 

[FORCED LOCAL] (LCF-)

 

 

 

 

 

Parameter

Possible values

 

 

Forced local switch

Function inactive:

[Forced local assign.] (FLO)

[No] (nO)

 

Assignment to a logic input LI1 ... LI14:

 

[LI1] (LI1) ... [LI14] (LI14)

 

Forced local mode is active when the input is at state 1.

 

 

Forced local channel

Forced local on stop.

[Forced local Ref.] (FLOC)

[No] (nO)

 

Assignment of the command to the terminals and of the reference to one of the analog inputs AI1

 

... AI4

 

[AI2 ref.] (AI2), [AI3 ref.] (AI3), [AI4 ref.] (AI4)

 

Assignment of the command to the terminals and of the reference to the frequency input (if card

 

present)

 

[Pulse Input] (PI)

 

Assignment of the reference [HMI Frequency ref.] (LFr) and of the command

 

(RUN/STOP/FWD/REV buttons) to the graphic display terminal

 

[HMI] (LCC)

 

 

 

In "forced local" state:

Any attempts to write the parameter via one of these channels is rejected (applies to command, reference and adjustment parameters).

However, the parameters can be read.

The drive does not register a communication fault.

On exiting "forced local" mode:

The drive copies the run commands, the direction and the forced local reference to the active channel (maintained).

Monitoring of the active command and reference channels resumes following a time delay [Time-out forc. local] (FLOt).

Drive control only takes effect once the drive has received the reference and the command.

The time delay [Time-out forc. local] (FLOt) (default value = 10 s) can be configured via the remote graphic display terminal:

Menu

Submenu

Parameter

 

 

 

[1.9 COMMUNICATION] (COM-)

[FORCED LOCAL] (LCF-)

[Time-out forc. local] (FLOt)

 

 

 

45