Fault parameters

Fault parameters

Code

 

 

Description

 

 

 

 

 

 

 

Errd

Parameter name:

CiA402 fault code

 

 

 

 

CiA402 name:

Error code

 

 

 

 

DRIVECOM name:

Malfunction code

 

 

 

 

 

 

 

 

 

 

Logic address:

8606 = 16#219E

 

Type:

WORD (listing)

 

CANopen index:

603F/0

 

Read/write:

R

 

INTERBUS index:

603F/0

 

Unit:

-

 

DeviceNet path:

29/01/0D (1)

 

 

 

 

 

8C/01/07 (2)

 

 

 

 

 

 

 

 

 

(1)ODVA standard path. It can be used for explicit messaging. Do not use it for configuring an assembly.

(2)Altivar path. To ensure better interchangeability, avoid using it for explicit messaging. This is the path that must be used for configuring an assembly.

Parameter conforming to CiA402 profile

Last fault that occurred. This parameter retains its value after the fault has disappeared and been acknowledged.

16#0000: No fault written to memory (nOF)

16#1000: Pre-charge relay control fault or charging resistor damaged (CrF1) or excessive motor current (OLF)

or motor overspeed fault (SOF)

or short-circuit output from braking unit (bUF) or braking resistor under excessive stress (bOF)

or short-circuit or grounding at the drive output (HdF) or internal microprocessor fault (InFE)

16#2230: Power component fault (SCF4)

16#2310: Overcurrent fault (OCF)

16#2311: Process overload (OLC)

16#2320: Short-circuit or grounding at the drive output (SCF1, SCF2, SCF5)

16#2330: Ground short-circuit (SCF3)

16#3110: Line supply overvoltage fault (OSF)

16#3120: Line supply undervoltage fault (USF)

16#3130: Input phase loss fault (PHF)

16#3310: DC bus overvoltage fault (ObF) or 1 output phase loss fault (OPF1) or 3 output phase loss fault (OPF3)

16#4210: Drive overheat fault (OHF, tJF)

16#4310: Overheating of motor probes detected (OtF1, OtF2, OtFL)

16#5000: Initialization of the drive is incomplete (InF7)

or fault on the electronic time measurement component (InFC) or output contactor fault (FCF1, FCF2)

or line contactor fault (LCF)

or DC bus charging fault (thyristors) (CrF2)

16#5100: The control section power supply is incorrect (InF8)

16#5210: Current measurements are incorrect (InF9) or input stage not operating correctly (InFA)

or drive temperature sensor not operating correctly (InFb) 16#5530: EEPROM non-volatile memory fault (EEF, EEF2) 16#6100: Internal fault (InF, InF1, InF2, InF3, InF4, HCF) 16#6300: Incorrect configuration (parameters) (CFF)

or invalid configuration (CFI)

or inconsistency between control card and power card (PtrF) 16#7000: The option installed in the drive is not recognized (InF6)

16#7300: Loss of the 4-20 mA reference on analog input AI2 (LFF2, LFF3, LFF4) or non-conforming signal on analog input AI2(AI2F)

or PTC probes open or short-circuited (PtF1, PtF2, PtFL) 16#7310: Encoder feedback fault (EnF)

or encoder feedback signal missing (SPF) 16#7510: Modbus communication fault (SLF1)

or fault communicating with the graphic display terminal (SLF3) 16#7520: Communication fault between option card and drive (ILF)

or communication fault on communication card (CnF)

100