Schneider Electric 61 user manual Log parameters, Description of last fault log, Code

Models: 61

1 131
Download 131 pages 6.3 Kb
Page 107
Image 107
Log parameters

Log parameters

Description of last fault log

Code

 

Description

 

 

 

 

 

 

dP0

Parameter name:

Fault code on last fault

 

 

 

 

 

 

 

 

Logic address:

7200 = 16#1C20

Type:

WORD (listing)

 

CANopen index:

202A/1

Read/write:

R

 

INTERBUS index:

5FB9/59

Unit:

-

 

DeviceNet path:

85/01/01

 

 

 

 

 

 

 

 

Value of the "Altivar fault code" (LFt) parameter, written to memory when the last fault occurred.

 

See the possible values of the "Altivar fault code" (LFt) parameter.

 

 

 

 

 

ULP0

Parameter name:

Power supply voltage on last fault

 

 

 

 

 

 

 

Logic address:

7270 = 16#1C66

Type:

UINT

 

CANopen index:

202A/47

Read/write:

R

 

INTERBUS index:

5FB9/98

Unit:

0.1 V

 

DeviceNet path:

85/01/47

 

 

 

 

 

 

 

 

Value of the "Power supply voltage" (ULn) parameter, written to memory when the last fault occurred.

 

 

 

 

 

LCP0

Parameter name:

Motor current on last fault

 

 

 

 

 

 

 

 

Logic address:

7240 = 16#1C48

Type:

INT

 

CANopen index:

202A/29

Read/write:

R

 

INTERBUS index:

5FB9/7D

Unit:

0.1 A

 

DeviceNet path:

85/01/29

 

 

 

 

 

 

 

 

Value of the "Motor current" (LCr) parameter, written to memory when the last fault occurred.

 

 

 

 

 

rFP0

Parameter name:

Output frequency on last fault

 

 

 

 

 

 

 

Logic address:

7250 = 16#1C52

Type:

INT

 

CANopen index:

202A/33

Read/write:

R

 

INTERBUS index:

5FB9/86

Unit:

0.1 Hz

 

DeviceNet path:

85/01/33

 

 

 

 

 

 

 

 

Value of the "Output frequency" (rFr) parameter, written to memory when the last fault occurred.

 

 

 

 

tHP0

Parameter name:

Motor thermal state on last fault

 

 

 

 

 

 

 

Logic address:

7280 = 16#1C70

Type:

UINT

 

CANopen index:

202A/51

Read/write:

R

 

INTERBUS index:

5FB9/A1

Unit:

1

 

DeviceNet path:

85/01/51

 

 

 

 

 

 

 

EP0

Parameter name:

Status word on last fault

 

 

 

 

 

 

 

 

Logic address:

7210 = 16#1C2A

Type:

WORD (bit register)

 

CANopen index:

202A/B

Read/write:

R

 

INTERBUS index:

5FB9/62

Unit:

-

 

DeviceNet path:

85/01/0B

 

 

 

 

 

 

 

Value of the "Status word" (EtA) parameter, written to memory when the last fault occurred.

See the possible values of the "Status word" (EtA) parameter.

107

Page 107
Image 107
Schneider Electric 61 user manual Log parameters, Description of last fault log, Code, Fault code on last fault