Fault parameters
Code |
|
|
| Description |
| |
|
|
|
|
|
| |
LFt | Parameter name: | Altivar fault code |
|
|
| |
|
|
|
|
|
| |
| Logic address: | 7121 = 16#1BD1 |
| Type: | WORD (listing) | |
| CANopen index: | 2029/16 |
|
| Read/write: | R |
| INTERBUS index: | 5FB9/58 |
|
| Unit: | - |
| DeviceNet path: | 84/01/7A |
|
|
|
|
|
|
|
|
| ||
| The last fault that occurred remains stored in the "Altivar fault code" (LFt) parameter, even if it disappears and even after | |||||
| the drive has been turned off and then on again. |
|
|
| ||
| 0: | (nOF) | No fault |
|
|
|
| 1: |
| Reserved |
|
|
|
| 2: [Control Eeprom] | (EEF1) | Internal memory fault, control card |
| ||
| 3: [Incorrect config.] | (CFF) | Option card changed or removed |
| ||
|
|
| Control card replaced by a control card configured on a drive with a different rating | |||
|
|
| The current configuration is inconsistent |
| ||
| 4: [Invalid config.] | (CFI) | Invalid configuration. The configuration loaded in the drive via the bus or | |||
|
|
| communication network is inconsistent |
| ||
| 5: [Modbus com.] | (SLF1) | Interruption in communication on the Modbus bus |
| ||
| 6: [internal com. link] | (ILF) | Communication fault between option card and drive | |||
| 7: [Com. network] | (CnF) | Communication fault on communication card |
|
8:[External
9:[Overcurrent] (OCF) Parameters in [SETTINGS]
|
| Inertia or load too high |
|
| Mechanical locking |
10: [Precharge] | (CrF1) | |
11: [Speed fdback loss] | (SPF) | Encoder feedback signal missing |
12: |
| Reserved |
13:[AI2
14: [PTC1 probe] | (PtF1) PTC1 probes open or shorted |
15:[PTC1 overheat] (OtF1) Overheating of the PTC1 probes detected
16: [Drive overheat] | (OHF) | Drive temperature too high |
17: [Motor overload] | (OLF) | Triggered by excessive motor current |
18: [Overbraking] | (ObF) | Braking too sudden or driving load |
19: [Mains overvoltage] | (OSF) | Line voltage too high |
|
| Disturbed line supply |
20:[1 output phase loss] (OPF1) Loss of one phase at drive output
21: [Input phase loss] | (PHF) | Drive incorrectly supplied or a fuse blown |
|
| Loss of one phase |
|
| |
|
| Unbalanced load |
|
| This protection only operates with the drive on load |
22: [Undervoltage] | (USF) | Line supply too low |
|
| Transient voltage dip |
|
| Damaged precharge resistor |
23:[Motor short circuit] (SCF1)
|
| Significant earth leakage current at the drive output if several motors are |
|
| connected in parallel |
24: [Overspeed] | (SOF) | Instability or driving load too high |
25: | (tnF) | Special motor or motor whose power is not suitable for the drive |
|
| Motor not connected to the drive |
26: [Rating error] | (InF1) | The power card is not the one stored |
27: [Incompatible PB] | (InF2) | The power card is incompatible with the control card |
28: [Internal serial link] | (InF3) | Communication fault between the internal cards |
29: [Internal MFG area] | (InF4) | Internal data inconsistent |
30:[Power EEprom] (EEF2) Internal memory fault, power card
31:[Impedant sh. circuit] (SCF2) Impedant
32:[Ground short circuit] (SCF3) Ground
33:[3 output phase loss] (OPF2) Motor not connected or motor power too low Output contactor open
Instantaneous instability in the motor current
34: [CAN com.] | (COF) Interruption in communication on the CANopen bus |