Fault parameters

Code

 

 

 

Description

 

 

 

 

 

 

 

LFt

Parameter name:

Altivar fault code

 

 

 

 

 

 

 

 

 

 

Logic address:

7121 = 16#1BD1

 

Type:

WORD (listing)

 

CANopen index:

2029/16

 

 

Read/write:

R

 

INTERBUS index:

5FB9/58

 

 

Unit:

-

 

DeviceNet path:

84/01/7A

 

 

 

 

 

 

 

 

 

 

The last fault that occurred remains stored in the "Altivar fault code" (LFt) parameter, even if it disappears and even after

 

the drive has been turned off and then on again.

 

 

 

 

0:

(nOF)

No fault

 

 

 

 

1:

 

Reserved

 

 

 

 

2: [Control Eeprom]

(EEF1)

Internal memory fault, control card

 

 

3: [Incorrect config.]

(CFF)

Option card changed or removed

 

 

 

 

Control card replaced by a control card configured on a drive with a different rating

 

 

 

The current configuration is inconsistent

 

 

4: [Invalid config.]

(CFI)

Invalid configuration. The configuration loaded in the drive via the bus or

 

 

 

communication network is inconsistent

 

 

5: [Modbus com.]

(SLF1)

Interruption in communication on the Modbus bus

 

 

6: [internal com. link]

(ILF)

Communication fault between option card and drive

 

7: [Com. network]

(CnF)

Communication fault on communication card

 

8:[External flt-LI/Bit](EPF1) Fault triggered by an external device, depending on user

9:[Overcurrent] (OCF) Parameters in [SETTINGS] (SEt-)and [1.4 MOTOR CONTROL] (drC-)menus are not correct

 

 

Inertia or load too high

 

 

Mechanical locking

10: [Precharge]

(CrF1)

Pre-charge relay control fault or charging resistor damaged

11: [Speed fdback loss]

(SPF)

Encoder feedback signal missing

12:

 

Reserved

13:[AI2 4-20mA loss] (LFF2) Loss of the 4-20 mA reference on analog input AI2

14: [PTC1 probe]

(PtF1) PTC1 probes open or shorted

15:[PTC1 overheat] (OtF1) Overheating of the PTC1 probes detected

16: [Drive overheat]

(OHF)

Drive temperature too high

17: [Motor overload]

(OLF)

Triggered by excessive motor current

18: [Overbraking]

(ObF)

Braking too sudden or driving load

19: [Mains overvoltage]

(OSF)

Line voltage too high

 

 

Disturbed line supply

20:[1 output phase loss] (OPF1) Loss of one phase at drive output

21: [Input phase loss]

(PHF)

Drive incorrectly supplied or a fuse blown

 

 

Loss of one phase

 

 

Three-phase ATV61 used on a single-phase line supply

 

 

Unbalanced load

 

 

This protection only operates with the drive on load

22: [Undervoltage]

(USF)

Line supply too low

 

 

Transient voltage dip

 

 

Damaged precharge resistor

23:[Motor short circuit] (SCF1) Short-circuit or grounding at the drive output

 

 

Significant earth leakage current at the drive output if several motors are

 

 

connected in parallel

24: [Overspeed]

(SOF)

Instability or driving load too high

25: [Auto-tuning]

(tnF)

Special motor or motor whose power is not suitable for the drive

 

 

Motor not connected to the drive

26: [Rating error]

(InF1)

The power card is not the one stored

27: [Incompatible PB]

(InF2)

The power card is incompatible with the control card

28: [Internal serial link]

(InF3)

Communication fault between the internal cards

29: [Internal MFG area]

(InF4)

Internal data inconsistent

30:[Power EEprom] (EEF2) Internal memory fault, power card

31:[Impedant sh. circuit] (SCF2) Impedant short-circuit

32:[Ground short circuit] (SCF3) Ground short-circuit

33:[3 output phase loss] (OPF2) Motor not connected or motor power too low Output contactor open

Instantaneous instability in the motor current

34: [CAN com.]

(COF) Interruption in communication on the CANopen bus

102