Incorrect configuration

Fault parameters

Code

 

Description

 

 

 

 

 

 

CIC

Parameter name:

Incorrect configuration

 

 

 

 

 

 

 

 

Logic address:

7130 = 16#1BDA

Type:

WORD (bit register)

 

CANopen index:

2029/1F

Read/write:

R

 

INTERBUS index:

5FB6/1A

Unit:

-

 

DeviceNet path:

84/01/83

 

 

 

 

 

 

 

 

bit 0: = 1: Change of rating

 

 

 

bit 1: Reserved (= 0 or 1)

 

 

 

 

bit 2: = 1: The network card has been removed

 

 

 

bit 3: = 1: Saving to the EEPROM non-volatile memory is inconsistent with power on

 

 

bit 4: = 1: The network card has been changed

 

 

 

bit 5: Reserved (= 0 or 1)

 

 

 

 

bit 6: = 1: The (Controller Inside) card has been removed

 

 

 

bit 7: = 1: The (Controller Inside) card has been changed

 

 

 

bit 8: Reserved (= 0 or 1)

 

 

 

 

bit 9: = 1: An I/O card has been removed

 

 

 

bit 10: = 1: The I/O card has been changed

 

 

 

bit 11: Reserved (= 0 or 1)

 

 

 

 

bit 12: = 1: An encoder card has been removed

 

 

 

bit 13: = 1: The encoder card has been changed

 

 

 

bit 14: Reserved (= 0 or 1)

 

 

 

 

bit 15: Reserved (= 0 or 1)

 

 

 

 

If one of these events occurs, the drive switches to [Incorrect config.] (CFF) fault mode and then automatically applies a

 

factory setting.

 

 

 

 

 

 

 

APF

Parameter name:

"Controller Inside" card fault code

 

 

 

 

 

 

 

Logic address:

7133 = 16#1BDD

Type:

UINT

 

CANopen index:

2029/22

Read/write:

R

 

INTERBUS index:

5FB0/99

Unit:

1

 

DeviceNet path:

84/01/86

 

 

 

 

 

 

 

 

The fault remains saved in the parameter, even if it disappears.

 

 

The parameter is reset after the drive is disconnected and then reconnected.

 

 

Consult the "Controller Inside" card manual.

 

 

 

 

 

 

 

CnF

Parameter name:

Network card fault code

 

 

 

 

 

 

 

 

Logic address:

7132 = 16#1BDC

Type:

UINT

 

CANopen index:

2029/21

Read/write:

R

 

INTERBUS index:

5FB0/98

Unit:

1

 

DeviceNet path:

84/01/85

 

 

 

 

 

 

 

The fault remains saved in the parameter, even if it disappears.

The parameter is reset after the drive is disconnected and then reconnected.

The possible values of this parameter depend on the network card protocol. Consult the manual for the corresponding card.