Configuration saving and switching

Restore configuration

The restore configuration command is executed using bit 2 of the extended control word (CMI).

Display

 

 

 

 

 

 

 

 

 

terminal

 

 

 

 

 

Modbus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current

 

 

 

CANopen

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

configuration

 

 

 

 

 

 

 

 

 

 

(RAM)

 

 

 

 

Network

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Extended control word:

Set to 1

Restore configuration (CMI,2)

 

Industrial

HMI

terminal

PLC

Configuration 0

(EEPROM)

Configuration 1

(EEPROM)

Configuration 2

(EEPROM)

Factory settings

The return to factory settings command is executed using bit 0 of the extended control word (CMI). The type of setting is determined by the active macro configuration parameter [Macro configuration] (CFG) and by the [PARAMETER GROUP LIST] (FrY) parameter which defines the parameter groups concerned.

Display terminal

Current

configuration

(RAM)

Extended control word:

Factory setting (CMI,0)

Modbus

CANopen

Network

Set to 1

Industrial

HMI

terminal

PLC

Configuration 0

(EEPROM)

Configuration 1

(EEPROM)

Configuration 2

 

 

 

Factory settings

 

 

 

(EEPROM)

 

 

 

 

 

 

 

 

 

 

 

 

[Macro configuration]

(CFG)

The restore command is only active if the drive is stopped, and not in "5-Operation enabled" state.