CiA402 profile

bStep 3

Check that the drive is in the "4 - Switched on" state.

Then send the "4 - Enable operation" command.

The motor can be controlled (send a reference not equal to zero).

If the power section line supply is still not present in the "4 - Switched on" state after a time delay[Mains V. time out] (LCt), the drive will switch to fault mode (LCF).

From all states

Bus or network

Control section power supply

 

Power section line supply

 

 

 

DRIVE

9Disablevoltage Shutdown 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entry into state chart

7

Fault reaction

 

 

 

 

 

 

 

 

 

 

 

 

 

active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Not ready to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switch on

 

 

 

8

 

 

Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

2

Switch on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

disabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disable voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shutdown 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7 or Quick stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Ready to

 

 

Disable voltage

 

 

 

 

 

 

10

 

 

switch on

 

 

or Quick stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Switch on 3

 

 

 

 

Shutdown

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

Switched on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M

 

Enable

4

 

 

Disable

 

 

 

 

 

 

 

 

 

operation

 

 

5 operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

Operation

 

 

11

 

 

6

Quick stop

 

 

 

 

 

 

 

 

 

 

enabled

 

 

 

 

active

 

 

 

 

 

 

Quick stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33

Page 33
Image 33
Schneider Electric 61 user manual Enable