Schneider Electric 61 Configuration saving and switching, Function parameters, Code, Description

Models: 61

1 131
Download 131 pages 6.3 Kb
Page 66
Image 66
Save configuration

Configuration saving and switching

Function parameters

Code

 

Description

 

 

 

 

 

 

SCS

Parameter name:

Save configuration

 

 

 

 

 

 

 

 

Logic address:

8001 = 16#1F41

Type:

WORD (listing)

 

CANopen index:

2032/2

Read/write:

R/WS

 

INTERBUS index:

5FBC/9A

 

 

 

DeviceNet path:

9C/01/9A

 

 

 

 

 

 

 

 

0 = No save

 

 

 

 

1 = Save to configuration no. 0

 

 

 

2 = Save to configuration no. 1

 

 

 

3 = Save to configuration no. 2

 

 

 

 

 

 

 

FCS

Parameter name:

Restore configuration

 

 

 

 

 

 

 

 

Logic address:

8002 = 16#1F42

Type:

WORD (listing)

 

CANopen index:

2032/3

Read/write:

R/WS

 

INTERBUS index:

5FBC/9B

 

 

 

DeviceNet path:

9C/01/9B

 

 

 

 

 

 

 

 

0 = No restore

 

 

 

 

1 = Restore configuration no. 0

 

 

 

2 = Restore configuration no. 1

 

 

 

3 = Restore configuration no. 2

 

 

 

64 = Factory setting

 

 

 

 

 

 

 

 

FrY

Parameter name:

Parameter groups

 

 

 

Terminal display:

[PARAMETER GROUP LIST]

 

 

 

 

 

 

 

 

Logic address:

3022 = 16#OBCE

Type:

WORD (bit register)

 

CANopen index:

2000/17

Read/write:

R/WS

 

INTERBUS index:

5FBC/06

Factory setting:

0

 

DeviceNet path:

70/01/17

 

 

 

 

 

 

 

 

Selection of menus to be loaded

 

 

 

bit 0: = 1: [All] (ALL): All parameters

 

 

 

bit 1: = 1: [Drive menu] (drM): The [1 DRIVE MENU] menu without [1.9 COMMUNICATION] and [1.14 CONTROL

 

INSIDE MENU]. In the [7 DISPLAY CONFIG.] menu, [Return std name] returns to [No]

 

bit 2: = 1: [Settings] (SEt): The [1.3 SETTINGS] menu without the [IR compensation] (UFr), [Slip compensation] (SLP)

 

and [Mot. therm. current] (ItH) parameters

 

 

 

bit 3: = 1: [Motor param] (MOt): Motor parameters:

 

 

 

[Rated motor power] (nPr) - [Rated motor volt.] (UnS) - [Rated mot. current] (nCr) - [Rated motor freq.] (FrS) -

 

[Rated motor speed] (nSP) - [Auto tuning] (tUn) - [Auto tuning state] (tUS) - [U0] (U0) to [U5] (U5) - [F1] (F1) to

 

[F5] (F5) - [V. constant power] (UCP) - [Freq. Const Power] (FCP) - [Nominal I sync.] (nCrS) - [Nom motor

 

spdsync] (nSPS) - [Pole pairs] (PPnS) - [Syn. EMF constant] (PHS) - [Autotune L d-axis] (LdS) - [Autotune L q-

 

axis] (LqS) - [Cust. stator R syn] (rSAS) - [IR compensation] (UFr) - [Slip compensation] (SLP) - the motor

 

parameters that can be accessed in [Expert] mode

 

 

 

The following options can only be accessed if [Config. Source] (FCSI) = [Macro-Conf](InI):

 

 

bit 4: = 1: [Comm. menu] (COM): The [1.9 COMMUNICATION] menu without either [Scan. IN1 address] (nMA1) to

 

[Scan. IN8 address] (nMA8) or [Scan.Out1 address] (nCA1) to [Scan.Out8 address] (nCA8)

 

bit 5: = 1: [Control Inside menu] (PLC): The [1.14 CONTROL INSIDE MENU] menu

 

 

bit 6: = 1: [Monitor config.] (MOn): The [6 MONITORING CONFIG.] menu

 

 

bit 7: = 1: [Display config.] (dIS): The [7 DISPLAY CONFIG.] menu

 

 

bits 8 to 15: Reserved (= 0 or 1)

 

 

 

 

 

 

 

66

Page 66
Image 66
Schneider Electric 61 Configuration saving and switching, Function parameters, Code, Description, Save configuration