AXIS A1001 Installation Guide

Reader I/O connectors DC output: 12 V DC, max 300 mA 2x 4 configurable inputs/outputs: Digital input: 0 to max 40 V DC Digital output: 0 to max 40 V DC, open drain, 100 mA

READER I/0 1 &2

Power connector

DC input: 10–30 V DC, max 26 W

Max load on outputs: 14 W

DC IN

Page 15

AWG 28–16 (CSA)

AWG 30–14 (CUL/UL)

Power & Relay connector

DC output: 12 V DC, max 500 mA

Relay: 30 V DC, max 700 mA

RELAY & PWR

Power lock connector

 

 

2x 12 V DC

V

DC,

0 V DC, floating, or 12

max total load: 500 mA

 

LOCK

Auxiliary connector

DC output: 3.3 V DC, max 100 mA

Digital input: 0 to max 40 V DC;

Digital output: 0 to max 40 V DC, open drain, 100 mA

AUX

Reader data connectors

Max cable length: 30 m (98.4 ft) RS485 full duplex

RS485 half duplex Wiegand

READER DATA 1 & 2

Door connectors

Digital input: 0 to max 40 V DC

DOOR IN 1 &2

Network Connector

RJ45, PoE IEEE 802.3af/

802.3at Type 1 Class 3

Max load on outputs: 7.5 W

Page 15
Image 15