Bryant 561C SPECIFICATIONS Continued, Unit Size-Series, Electrical, Compressor & Refrigerant

Models: 561C

1 28
Download 28 pages 31.71 Kb
Page 5
Image 5
SPECIFICATIONS Continued

SPECIFICATIONS Continued

UNIT SIZE-SERIES

561C036-A, B, E

561C036-B, D

 

561C036-B

561C042-A, B

561C042-B, C

561C042-B

Operating Weight (Lb)

129/138/138

129/133

 

133

138/142

142

 

ELECTRICAL

 

 

 

 

 

 

 

 

Unit Volts—Hertz—Phase

208-230—60—1

208/230—60—3

 

460—60—3

208-230—60—1

208/230—60—3

460—60—3

Operating Voltage Range*

197—253

187—253

 

414—506

197—253

187—253

414—506

Compressor— Rated Load Amps

16.7/14.8/16.0

10.0/10.6

 

5.1

20.5/19.7

13.6/12.4

6.2

 

 

Locked Rotor Amps

95.0/86.0/81.0

75.0/64.5

 

33.0

115.0/102.0

91.0/90.0

42.0

 

Condenser Fan Motor—Full Load Amps

1.4

1.4

 

0.8

1.4

1.4

0.8

 

Min Unit Ampacity for Wire Sizing

22.3/19.9/21.4

13.9/14.7

 

7.2

27.0/26.0

18.4/16.9

8.6

 

Min Wire Size (60°C Copper) AWG†

12

14

 

14

10

14

14

 

Min Wire Size (75°C Copper) AWG†

12

14

 

14

10

14

14

 

Max Wire Length (60°C) (Ft)‡

55/55/58

65/60

 

250

70/75

45/50

210

 

Max Wire Length (75°C) (Ft)‡

50/55/55

62/55

 

238

70

45/50

200

 

Max Branch Circuit Fuse Size**

30

20

 

15

40

25

15

 

COMPRESSOR & REFRIGERANT

 

 

 

 

 

 

 

 

Compressor— Manufacturer

Millennium/

Copeland/

 

Copeland

Millennium/

Copeland/

Copeland

Copeland/Bristol

Millennium

 

Copeland

Millennium

 

 

 

 

 

 

 

 

Scroll/

Reciprocating/

 

 

Scroll/

Reciprocating/

 

 

 

Type

Reciprocating/

 

Reciprocating

Reciprocating

 

Scroll

 

Reciprocating

Scroll

 

 

Reciprocating

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature and Current Protection

 

 

 

Internal Line Break

 

 

 

 

 

R-22 and 4.63/

R-22 and 5.00/

 

 

R-22 and 5.00/

R-22 and 5.13/

R-22 and 5.13

Refrigerant—Type and Amount @ 15 Ft

5.00/4.60

4.63

R-22 and 5.00

5.13

5.00

 

 

CONDENSER COIL & FAN

 

 

 

 

 

 

 

 

Coil Face Area (Sq Ft)

 

9.1

 

 

 

10.7

 

 

 

 

20—1—2/

25—1—2/

 

 

22—1—3/

25—1—3/

 

 

Fins Per In.—Rows—Circuit

25—1—2/

 

25—1—2

25—1—3

20—1—2

 

25—1—3

22—1—3

 

 

25—1—2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/5 and 1125/

 

 

 

 

 

 

 

Fan Motor—PSC Type, HP and RPM

1100/1125

1/5 and 1125

 

1/4 and 1125

1/5 and 1125

1/4 and 1125

Volts—Hertz—Phase

208/230—60—1

 

460—60—1

208/230—60—1

460—60—1

Condenser Airflow (CFM)

 

2500

 

 

 

3400

 

 

OPTIONAL EQUIPMENT

 

 

 

 

 

 

 

 

Coastal Filter

 

 

 

KAACF0401MED

 

 

 

Time-Delay Relay

 

 

 

KAATD0101TDR

 

 

 

Cycle Protector

Standard/

KSACY0101AAA

Standard/

KSACY0101AAA

KSACY0101AAA/

KSACY0101AAA

 

 

KSACY0101AAA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low-Ambient Controller

 

 

 

P251-0083 (RCD)

 

 

 

Crankcase Heater

KAACH1201AAA /

KAACH1201AAA/

KAACH1101AAA

KAACH1201AAA/KAACH1001AAA

KAACH1101AAA

KAACH1001AAA/KAACH1001AAA

KAACH1001AAA

Inlet Grille Kit

KSABG0804CSM

 

 

 

KSABG1004CSM

 

 

 

Start Assist—Capacitor/Relay Type††

KSAHS1501AAA/

N/A

 

KSAHS1501AAA/

N/A

KSAHS1001AAA/

 

 

KSAHS1301AAA

 

 

KSAHS1101AAA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start Assist—PTC Type

KAACS0201PTC

N/A

 

KAACS0201PTC

N/A

Sound Hood

KSASH1901CYL/

KSASH1901CYL/

 

N/A

KSASH1901CYL /KSASH1201COP

KSASH1201COP

KSASH1201COP/

N/A

 

 

 

KSASH2001BRL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TXV (RPB)

 

 

 

KAATX0501RPB

 

 

 

TXV (Hard Shutoff)††

 

 

 

KSATX0601HSO

 

 

 

Low-Pressure Switch

 

 

 

KAALP0101LPS

 

 

 

High-Pressure Switch

 

 

 

KSAHI0101HPS

 

 

 

Filter Drier

P502-8083S (RCD)

 

P502-8163S (RCD)

Evaporator Freeze Thermostat‡‡

 

 

 

KAAFT0101AAA

 

 

 

Liquid-Line Solenoid Valve††

 

 

 

KAALS0101LLS

 

 

 

Winter Start Control‡‡

 

 

 

KAAWS0101AAA

 

 

 

MotorMaster® Control***

32LT660004 (RCD)

32LT660005 (RCD)

32LT660004 (RCD)

32LT660005 (RCD)

Ball Bearing Fan Motor

HC40GE230 (RCD)

HC40GE461 (RCD)

HC40GE230 (RCD)

HC40GE461 (RCD)

Thermostat, Auto Changeover,

 

 

 

 

 

 

 

 

Non-Programmable, °F/°C, 1-Stage Heat,

 

 

 

 

 

 

 

 

1-Stage Cool

 

 

 

TSTATBBNAC01-B

 

 

 

Thermostat, Auto Changeover,

 

 

 

 

 

 

 

 

7-Day Programmable, °F/°C,

 

 

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

 

TSTATBBPAC01-B

 

 

 

Builder’s Thermostat, Manual Changeover,

 

 

 

 

 

 

 

 

Non-Programmable, °F/°C,

 

 

 

 

 

 

 

 

1-Stage Heat, 1-Stage Cool

 

 

 

TSTATBBBAC01-B

 

 

 

Outdoor Air Temperature Sensor

 

 

 

TSTATXXSEN01-B

 

 

 

Backplate for Non-Programmable Thermostat

 

 

 

TSTATXXNBP01

 

 

 

Backplate for Programmable Thermostat

 

 

 

TSTATXXPBP01

 

 

 

Backplate for Builder’s Thermostat

 

 

 

TSTATXXBBP01

 

 

 

Thermostat Conversion Kit (4 to 5 wire)

 

 

 

TSTATXXCNV10

 

 

 

See notes on page 7.

 

—5—

 

 

 

 

 

 

Page 5
Image 5
Bryant 561C warranty SPECIFICATIONS Continued, Unit Size-Series, Electrical, Compressor & Refrigerant, Condenser Coil & Fan