ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued
9. High-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 ± 10 psig and resets at 298 ± 20 psig. Provides protection against compressor damage due to loss of outdoor airflow. To prevent rapid compressor recycling, Cycle Protector can be used with this switch.
SUGGESTED USE: Installations exposed to very ‘‘dirty’’ outdoor air.
Installations where condenser inlet air temperature exceeds 125°F (51.7°C).
10.Inlet Grille Kit
A
SUGGESTED USE: For greater protection against inclement weather, incidental damage, and vandalism.
11.Liquid-Line Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) and which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.
Note: Compressor Start
SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. In certain
12.Low-Ambient Controller
The control will maintain working head pressure at
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).
13.Low-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on low side of refrigerant circuit. Cycles compressor off if refrigerant pressure drops to about 27 psig. Prevents indoor coil
SUGGESTED USE: Where indoor coil is exposed to ‘‘dirty’’ air.
All commercial installations.
14.MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing temperature during operation in cooling mode only. For outdoor temperatures down to
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F.
All commercial installations.
15.Outdoor Air Temperature Sensor
A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat
SUGGESTED USE: All corporate programmable thermostats.
16.Sound Hood
Wraparound sound attenuation cover for the compressor. Reduces unit sound level by about 2 dBA.
SUGGESTED USE: Unit installed closer than 15 ft to quiet
Unit installed between 2 houses less than 10 ft apart.
17.Thermostatic Expansion Valve (TXV)
A modulating
SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. Required for use on all zoning systems.
18.Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory. Required for use on all zoning systems.
19.Winter Start Control
An SPST delay relay which bypasses the
SUGGESTED USE: All air conditioners where