*Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.

† If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60 or 75°C (140 or 167°F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than

10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

‡ Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.

**Time-delay fuse or circuit breaker.

††Start assist capacitor and relay required when using liquid solenoid valve or hard shutoff TXV (except 036 and 042, Series A; 048 and 060, Series A/B single phase; and all 3-phase units). Do not use hard shutoff TXV with liquid solenoid valve.

‡‡ Use with low-ambient controller.

***Fan motor with ball bearings required. N/A—Not Applicable

NOTES: 1. All motors/compressors contain internal overload protection.

2.Copper wire must be used from service disconnect to unit.

3.Control circuit is 24v on all units and requires external power source.

ACCESSORY USAGE GUIDELINE

 

REQUIRED FOR

REQUIRED FOR

REQUIRED FOR

 

LOW-AMBIENT

LONG-LINE

SEA COAST

 

APPLICATIONS

APPLICATIONS*

APPLICATIONS

ACCESSORY

(Below 55°F)

(Over 50 Ft)

(Within 2 Miles)

 

 

 

 

Crankcase Heater

Yes

Yes

No

 

 

 

 

Evaporator Freeze Thermostat

Yes

No

No

 

 

 

 

Winter Start Control

Yes†

No

No

 

 

 

 

Accumulator

No

No

No

 

 

 

 

Compressor Start Assist

Yes

Yes

No

Capacitor and Relay

 

 

 

 

 

 

 

Low Ambient Controller

 

 

 

or

Yes

No

No

MotorMaster® Control

 

 

 

 

 

 

 

Wind Baffle

See Low-Ambient Instructions

No

No

 

 

 

 

Coastal Filter

No

No

Yes

 

 

 

 

Support Feet

Recommended

No

Recommended

 

 

 

 

Liquid-Line Solenoid Valve

 

See Long-Line

 

or

No

Application

No

Hard Shutoff TXV

 

Guideline

 

 

 

 

 

Ball Bearing Fan Motor

Yes

No

No

 

 

 

 

*For tubing line sets between 50 and 175 ft, refer to Residential’s Split Systems Long-Line Application Guidelines.

† Only when low-pressure switch is used.

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

1. Ball Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.

SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.

2.Coastal Filter

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.

SUGGESTED USE: In geographic areas where salt damage could occur.

3.Compressor Start Assist—Capacitor/Relay Type

Start capacitor and start relay which gives ‘‘hard’’ boost to compressor motor at each start-up.

SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105°F (40.6°C).

Replacement installations with hard shutoff expansion valve on indoor coil.

Installations where Liquid-Line Solenoid Valve has been added.

4.Compressor Start Assist—PTC Type

Solid-state electrical device which gives a ‘‘soft’’ boost to compressor motor at each start-up.

SUGGESTED USE: Installations with marginal power supply.

Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.

5.Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication

on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. SUGGESTED USE: When interconnecting tube length exceeds 50 ft.

When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with Low-Ambient Controller.) All commercial installations.

6.Cycle Protector

Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has

been interrupted for any reason, including normal room thermostat cycling. SUGGESTED USE: Installations in areas where power interruptions are frequent.

Where user is likely to ‘‘play’’ with the room thermostat. All commercial installations.

Installations where interconnecting tube length exceeds 50 ft. High-rise applications.

7. Evaporator Freeze Thermostat

An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.

SUGGESTED USE: All units where Winter Start Control has been added.

8. Filter Drier

A device for removing contaminants from refrigerant circulating in an air conditioner: 1-direction flow.

SUGGESTED USE: All split-system units.

—7—

Page 7
Image 7
Bryant 561C warranty Accessory Usage Guideline, Required for LOW-AMBIENT LONG-LINE SEA Coast, Applications