*Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.
† If wire is applied at ambient greater than 30°C (86°F), consult Table
The ampacity of
10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).
‡ Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
**
††Start assist capacitor and relay required when using liquid solenoid valve or hard shutoff TXV (except 036 and 042, Series A; 048 and 060, Series A/B single phase; and all
‡‡ Use with
***Fan motor with ball bearings required.
NOTES: 1. All motors/compressors contain internal overload protection.
2.Copper wire must be used from service disconnect to unit.
3.Control circuit is 24v on all units and requires external power source.
ACCESSORY USAGE GUIDELINE
| REQUIRED FOR | REQUIRED FOR | REQUIRED FOR | |
|
|
| SEA COAST | |
| APPLICATIONS | APPLICATIONS* | APPLICATIONS | |
ACCESSORY | (Below 55°F) | (Over 50 Ft) | (Within 2 Miles) | |
|
|
|
| |
Crankcase Heater | Yes | Yes | No | |
|
|
|
| |
Evaporator Freeze Thermostat | Yes | No | No | |
|
|
|
| |
Winter Start Control | Yes† | No | No | |
|
|
|
| |
Accumulator | No | No | No | |
|
|
|
| |
Compressor Start Assist | Yes | Yes | No | |
Capacitor and Relay | ||||
|
|
| ||
|
|
|
| |
Low Ambient Controller |
|
|
| |
or | Yes | No | No | |
MotorMaster® Control |
|
|
| |
|
|
|
| |
Wind Baffle | See | No | No | |
|
|
|
| |
Coastal Filter | No | No | Yes | |
|
|
|
| |
Support Feet | Recommended | No | Recommended | |
|
|
|
| |
| See |
| ||
or | No | Application | No | |
Hard Shutoff TXV |
| Guideline |
| |
|
|
|
| |
Ball Bearing Fan Motor | Yes | No | No | |
|
|
|
|
*For tubing line sets between 50 and 175 ft, refer to Residential’s Split Systems
† Only when
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
1. Ball Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
SUGGESTED USE: Required on all units where
2.Coastal Filter
A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.
SUGGESTED USE: In geographic areas where salt damage could occur.
3.Compressor Start Assist—Capacitor/Relay Type
Start capacitor and start relay which gives ‘‘hard’’ boost to compressor motor at each
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.
Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil.
Installations where
4.Compressor Start Assist—PTC Type
SUGGESTED USE: Installations with marginal power supply.
Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.
5.Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication
on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control. SUGGESTED USE: When interconnecting tube length exceeds 50 ft.
When unit will be operated below 55°F (12.8°C) outdoor air temperature. (Use with
6.Cycle Protector
been interrupted for any reason, including normal room thermostat cycling. SUGGESTED USE: Installations in areas where power interruptions are frequent.
Where user is likely to ‘‘play’’ with the room thermostat. All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
7. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches
SUGGESTED USE: All units where Winter Start Control has been added.
8. Filter Drier
A device for removing contaminants from refrigerant circulating in an air conditioner:
SUGGESTED USE: All