SPECIFICATIONS
| UNIT  | 
 | |||||
| Operating Weight (Lb) | 113/115 | 
 | 115/117 | 124/133 | 124 | |
| ELECTRICAL | 
 | 
 | 
 | 
 | 
 | |
| Unit  | 
 | 
 | 
 | |||
| Operating Voltage Range* | 
 | 
 | 
 | |||
| Compressor— Rated Load Amps | 9.6/9.0 | 
 | 10.7/11.6 | 14.2/14.8 | 9.4 | |
| 
 | Locked Rotor Amps | 49.0/48.0 | 
 | 56.0/60.0 | 75.0/73.0 | 68.0 | 
| Condenser Fan  | 0.8 | 
 | 1.0 | 0.8 | 0.8 | |
| Min Unit Ampacity for Wire Sizing | 12.8/12.1 | 
 | 14.4/15.5 | 18.6/19.3 | 12.6 | |
| Min Wire Size (60°C Copper) AWG† | 
 | 
 | 
 | 14 | 
 | |
| Min Wire Size (75°C Copper) AWG† | 
 | 
 | 
 | 14 | 
 | |
| Max Wire Length (60°C) (Ft)‡ | 61/65 | 
 | 50/49 | 40 | 70 | |
| Max Wire Length (75°C) (Ft)‡ | 58/61 | 
 | 50/47 | 40/38 | 65 | |
| Max Branch Circuit Fuse Size** | 20/15 | 
 | 20 | 25 | 15 | |
| COMPRESSOR & REFRIGERANT | 
 | 
 | 
 | 
 | 
 | |
| Compressor— Manufacturer | 
 | 
 | Copeland/Bristol | 
 | Copeland | |
| 
 | Type | 
 | 
 | Reciprocating | 
 | |
| Temperature and Current Protection | 
 | 
 | Internal Line Break | 
 | ||
| 
 | ||||||
| CONDENSER COIL & FAN | 
 | 
 | 
 | 
 | 
 | |
| Coil Face Area (Sq Ft) | 5.6 | 
 | 6.2 | 
 | 7.4 | |
| Fins Per  | 
 | |||||
| 
 | ||||||
| 
 | 
 | 
 | 
 | |||
| Fan  | 1/8 and 1500 | 
 | 1/6 and 1500 | 1/10 and 1125 | 1/10 and 1125 | |
| 
 | 
 | 
 | ||||
| Condenser Airflow (CFM) | 1400/1500 | 
 | 1550/1600 | 2000 | 1700 | |
| OPTIONAL EQUIPMENT | 
 | 
 | 
 | 
 | 
 | |
| Coastal Filter | KAACF0601SML | KAACF0401MED | ||||
| 
 | 
 | KAATD0101TDR | 
 | |||
| Cycle Protector | 
 | 
 | KSACY0101AAA | 
 | ||
| 
 | N/A | |||||
| Crankcase Heater | 
 | 
 | KAACH1001AAA | 
 | ||
| Inlet Grille Kit | KSABG0105CMC | 
 | KSABG0205CMC | KSABG0604CSM | 
 | |
| Start  | KSAHS0901AAA | 
 | KSAHS1001AAA/KSAHS0901AAA/KSAHS0901AAA | N/A | ||
| Start  | 
 | 
 | KAACS0201PTC | 
 | N/A | |
| Sound Hood | 
 | N/A | N/A / KSASH1301TEC/ | N/A / KSASH1301TEC | ||
| 
 | KSASH2001BRL | |||||
| 
 | 
 | 
 | 
 | 
 | 
 | |
| TXV (RPB) | KAATX0201RPB | 
 | KAATX0301RPB | KAATX0401RPB | ||
| TXV (Hard Shutoff)†† | 
 | 
 | KSATX0601HSO | 
 | ||
| 
 | 
 | KAALP0101LPS | 
 | |||
| 
 | 
 | KSAHI0101HPS | 
 | |||
| Filter Drier | 
 | 
 | 
 | |||
| Evaporator Freeze Thermostat‡‡ | 
 | 
 | KAAFT0101AAA | 
 | ||
| 
 | 
 | KAALS0101LLS | 
 | |||
| Winter Start Control‡‡ | 
 | 
 | KAAWS0101AAA | 
 | ||
| MotorMaster® Control*** | 
 | N/A | 32LT660004 (RCD) | |||
| Ball Bearing Fan Motor | 
 | N/A | HC34GE231 (RCD) | |||
| Thermostat, Auto Changeover, | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | ||||
| Thermostat, Auto Changeover, | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | ||||
| Builder’s Thermostat, Manual Changeover, | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | ||
| 
 | 
 | 
 | ||||
| Thermidistat Control, Programmable/ | 
 | 
 | 
 | 
 | 
 | |
| 
 | 
 | 
 | 
 | 
 | ||
| Humidity Control | 
 | 
 | 
 | |||
| Outdoor Air Temperature Sensor | 
 | 
 | 
 | |||
| Backplate for  | 
 | 
 | 
 | 
 | 
 | |
| Thermostat | 
 | 
 | TSTATXXNBP01 | 
 | ||
| Backplate for Programmable Thermostat | 
 | 
 | TSTATXXPBP01 | 
 | ||
| Backplate for Builder’s Thermostat | 
 | 
 | TSTATXXBBP01 | 
 | ||
| Thermostat Conversion Kit (4 to 5 wire) | 
 | 
 | TSTATXXCNV10 | 
 | ||
See notes on page 7.