Features--Digital Output Mapping

Analog Input module

Features--Digital Output Mapping

If users want to use Digital Output function, ADAM utility is available for setting specifically which module, channel or slot to receive the alarm signals.

Figure 4-36: Digital Output Mapping

1: High Alarm State--Set Alarm state to "Latch" or "Disable".

2: High Alarm Limit--Set Alarm limit from 0 to 4,294,967,295.

3: High Alarm Output Mode--Enable or Disable D.O. Mapping.

4: High Alarm Output Slot--Users can select D.O Modules such as ADAM-5050, ADAM-5055, ADAM-5056, ADAM-5060, ADAM- 5068 for the alarm signal to be sent through.

5: High Alarm Output Channel--Select Alarm Output Channel

6: Clear Latch Alarm--Users can select "Enable" or "Disable" option. When selecting "Enable", the latch will be relieved and the alarm state will return to normal. Once the alarm state returns to normal, the Clear Latch Alarm will return to "Disable".