the driver could be disabled before transmission is complete, resulting in data corruption. If the time is set too long, the 
Table 1: RS-485  Timeout Selection
Baud Rate  | Pos. 1  | Pos. 2  | Pos. 3  | Pos. 4  | Pos. 5  | R9  | Time(ms)  | 
1200  | ON  | OFF  | OFF  | OFF  | OFF  | 820 KΩ  | 8.20  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
2400  | ON  | OFF  | OFF  | OFF  | OFF  | 430 KΩ  | 4.30  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
4800  | OFF  | OFF  | OFF  | OFF  | ON  | Not Used  | 2.20  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
9600  | OFF  | OFF  | OFF  | ON  | OFF  | Not Used  | 1.30  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
19.2K  | OFF  | OFF  | ON  | OFF  | OFF  | Not Used  | 0.56  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
38.4K  | OFF  | ON  | OFF  | OFF  | OFF  | Not Used  | 0.27  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
57.6K  | ON  | OFF  | OFF  | OFF  | OFF  | Not Used  | 0.22  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
76.8K  | ON  | OFF  | ON  | ON  | OFF  | Not Used  | 0.14  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
115.2K  | ON  | ON  | ON  | OFF  | OFF  | Not Used  | 0.10  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
153.6K  | ON  | OFF  | OFF  | OFF  | OFF  | 6.2 KΩ  | 0.06  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
230.4K  | ON  | OFF  | OFF  | OFF  | OFF  | 4.3 KΩ  | 0.04  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
460.8K  | ON  | OFF  | OFF  | OFF  | OFF  | 2.2 KΩ  | 0.02  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
  | 
Position 6 of SW1 sets the unit as a “Repeating” module or a “Terminating” module. When the FOSTCDR is set as a “Repeating” module, data arriving on the Fiber Optic receiver is repeated back out the transmitter. When set as a “Terminating” module, data arriving at the Fiber optic receiver is not sent back out the Fiber Optic transmitter. Position 6 must be turned “On” when the FOSTCDR is to be used as one of the Slaves in a 
4  | FOSTCDR2999 Manual  | 
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph