Figure 3-3 Battery Installation
Bolt
Nut
Red Cable
Maximum Height:
PC32Ri = 5.2 in (131mm)
PC43Ri = 6.4 in (162mm)
Battery Band
Battery Base
Flange
Bolt
Flange
Bolt
Maximum Width: | Maximum Depth: | |
PC32Ri = 2.8 in (71mm) | ||
PC32Ri = 4.5 in (114mm) | ||
PC43Ri = 3.2 in (82mm) | ||
PC43Ri = 5.4 in (136mm) | ||
|
5.Secure the battery in position using the Battery Band shown in Figure
6.Do not lay tools or metal parts on top of batteries.
7.Disconnect the battery’s ground terminal before working in the vicinity of the battery or battery wires. Contact with the battery can result in electrical shock when a tool accidently touches the positive battery terminal or wire. The risk of such shock is reduced when the ground lead is removed during installation and maintenance.
Recommended Engine Oil and Battery Type
When replacing batteries, use only the recommended battery for your generator, see Table
Table 3-1
MODEL | SUMMER | WINTER | OIL CAPACITY | RECOMMENDED BATTERY |
|
OIL | OIL | qt (liter) |
| ||
|
|
| |||
|
|
|
|
| |
PC32Ri | SAE. 30 | 5W/30 | 0.63 (0.6) | Interstate YTZ7S − 12Volt − 6 AmpHour | |
PC43RI | SAE. 30 | 5W/30 | 1.0 (1.0) | Interstate YTX14AHL−BS − 12Volt − 12 | AmpHour |
Use of Electric Motor Loads
Electric motors require much more current (amperes) to start them than to keep them running. Some motors, particularly split−phase motors are very difficult to start and require 5 to 7 times more current to start them. Repulsion−induction type motors are the easiest to start and normally only require 2 to 3 times as much current to start them.
Most fractional horsepower motors take about the same amount of current to start them and keep them running. This is true whether they are the repulsion−induction type motor, capacitor type motor, or the split−phase type motor.
Other factors that influence the amount of current needed to start a motor are:
1.The type of load connected to the motor. If the electric motor is connected to a hard starting load such as an air compressor it will require more starting current. If the same electric motor is connected to a light load such as a heater or power saw it will require less starting current.
2.The brand or design of the electric motor. The expected starting current for a particular size motor will vary depending on the brand of the electric motor as well as the type of electric motor (Split Phase, capacitor, Repulsion−induction type, etc.)
3.The condition of the electric motor. A clean motor with free turning bearings will require less starting currents than a similar type motor that is dirty and the bearings are not as free turning as they used to be.
MN2403 | Receiving & Installation |