3.4Externally Mounted Battery Return Busbar
The battery return busbar is designed to mount on the overhead racking for 6000 A systems and top cabled 1500, 3000 or 4000 A power systems. It can also be mounted on a wall or on the floor below the raised floor for bottom cabled 1500, 3000 or 4000 A power systems (which are assumed to be installed on a raised, computer type floor).
3.4.1Mechanical Specifications of the External Battery Return Busbar
The external battery return busbar kit consists of a group of single busbar laminations and attachment hardware assembled as shown in Figure 17 (6000 A shown). The kit can grow verti- cally in such a way as to maintain the
Table 22 Mechanical specifications of a single lamination
Figure | Length | Width | Thickness |
|
|
|
|
Figure 17 | 863.6 mm | 152.4 mm | 12.7 mm |
| (34 inches) | (6 inches) | (0.5 inches) |
|
|
|
|
Figure 17 Top and side views of the external battery return busbar
6” (152 mm)
Top view of the external ground bar
Future growth as required |
34” (864 mm) |
6” | Smaller busbar for |
small wires and cables |
Available
configurations:
= 1500* & 3000 A
= 4000 A |
= 6000 A
Side view of the external ground bar installed on
auxiliary framing above the power system
NOTE
All bars and details are 0.5 in. thick.
*For a 1500 A system, only the bottom level is provided for the external battery return ground bar.
3.4.2Electrical Specifications of the External Battery Return Busbar
A single busbar lamination has a current carrying capacity of 3000 A.