3.7.3Electrical Specifications of the Helios Rectifiers 200I/48 and 200E/48
The electrical specifications of the Helios Rectifiers 200I/48 and 200E/48 are listed in Table 27.
Table 27 Electrical specifications of the Helios Rectifiers 200I/48 and 200E/48
Parameter | Specification |
|
|
Input voltage | Helios Rectifier 200I/48: |
| 380/415 V AC, three phase, |
| Input voltage range: 330 to 475 V AC |
| Helios Rectifier 200E/48: |
| 480 V AC, three phase, |
| Input voltage range: 430 to 520 V AC |
|
|
Input current | Helios Rectifier 200I/48: 18.3 A RMS nominal at 380 V AC input and |
| output (24 A RMS worst case) |
| Helios Rectifier 200E/48: 15 A RMS nominal at 480 V AC input and |
| output (17 A RMS worst case) |
|
|
Input protection | A 3 pole / 25 A circuit breaker opens all three lines. |
|
|
Recommended AC | 30 A, 3 pole AC circuit breaker |
service input |
|
|
|
Output voltage | Float: |
| Equalize: 0 to 4 V DC above Float |
| Maximum: |
|
|
Output current | 200 A nominal |
| Adjustable between 100 and 210 A |
|
|
Output protection | The rectifier is protected by a 250 A circuit breaker at the output. |
| The output current is limited to a value adjustable from 50% to 105% of the rated |
| capacity of the rectifier. This circuit is factory set to 205 A. |
|
|
Output regulation | The rectifier output voltage is automatically regulated to remain within ±0.5% of the |
| selected value under all load conditions and within the specified input voltage, |
| frequency, and ambient temperature ranges. And within + 1% for any combinations of |
| specified input, output and environmental conditions. |
|
|
Efficiency | Efficiency is better than 89% at nominal input voltage and an output load greater than |
| 80 A. |
|
|
Power factor | Power factor is better than 0.99 at nominal input voltage and an output load greater |
| than 80 A. |
|
|
Electromagnetic | The rectifier meets the FCC requirements for conducted and radiated EMI for Class |
interference (EMI) | “B” equipment. |
|
|
Heat dissipation | 1,335 W (4,558 Btu/hr) at |
|
|
Total harmonic | THD is less than 5% between half load and full load at nominal input voltage |
distortion (THD) |
|
|
|
3.7.4Standards
The following standards also apply to the rectifiers:
•ANSI Std. C62.41/IEEE Std.
•ANSI Std. C82.41 oscillatory surge 2500 V, 0.5 ms impulse, 100kHz positive/negative oscillat- ing decay
•Bellcore
•
•CISPR 22, Class A
•CE mark
24 Specifications