Liebert 6000 A, 3000, 4000, 1500 user manual 3.7.4Standards

Models: 3000

1 59
Download 59 pages 52.87 Kb
Page 30
Image 30
3.7.4Standards

3.7.3Electrical Specifications of the Helios Rectifiers 200I/48 and 200E/48

The electrical specifications of the Helios Rectifiers 200I/48 and 200E/48 are listed in Table 27.

Table 27 Electrical specifications of the Helios Rectifiers 200I/48 and 200E/48

Parameter

Specification

 

 

Input voltage

Helios Rectifier 200I/48:

 

380/415 V AC, three phase, 47-63 Hz

 

Input voltage range: 330 to 475 V AC

 

Helios Rectifier 200E/48:

 

480 V AC, three phase, 47-63 Hz

 

Input voltage range: 430 to 520 V AC

 

 

Input current

Helios Rectifier 200I/48: 18.3 A RMS nominal at 380 V AC input and -54 V DC, 200 A

 

output (24 A RMS worst case)

 

Helios Rectifier 200E/48: 15 A RMS nominal at 480 V AC input and -54 V DC, 200 A

 

output (17 A RMS worst case)

 

 

Input protection

A 3 pole / 25 A circuit breaker opens all three lines.

 

 

Recommended AC

30 A, 3 pole AC circuit breaker

service input

 

 

 

Output voltage

Float: -46 to -58 V DC

 

Equalize: 0 to 4 V DC above Float

 

Maximum: -60 V DC

 

 

Output current

200 A nominal

 

Adjustable between 100 and 210 A

 

 

Output protection

The rectifier is protected by a 250 A circuit breaker at the output.

 

The output current is limited to a value adjustable from 50% to 105% of the rated

 

capacity of the rectifier. This circuit is factory set to 205 A.

 

 

Output regulation

The rectifier output voltage is automatically regulated to remain within ±0.5% of the

 

selected value under all load conditions and within the specified input voltage,

 

frequency, and ambient temperature ranges. And within + 1% for any combinations of

 

specified input, output and environmental conditions.

 

 

Efficiency

Efficiency is better than 89% at nominal input voltage and an output load greater than

 

80 A.

 

 

Power factor

Power factor is better than 0.99 at nominal input voltage and an output load greater

 

than 80 A.

 

 

Electromagnetic

The rectifier meets the FCC requirements for conducted and radiated EMI for Class

interference (EMI)

“B” equipment.

 

 

Heat dissipation

1,335 W (4,558 Btu/hr) at -54 V DC, 200 A output

 

 

Total harmonic

THD is less than 5% between half load and full load at nominal input voltage

distortion (THD)

 

 

 

3.7.4Standards

The following standards also apply to the rectifiers:

ANSI Std. C62.41/IEEE Std. 587-1980, Class A and B lightning surge 6000 V, 3000 A, 1.2 x 50 ms impulse, 10 hits per second

ANSI Std. C82.41 oscillatory surge 2500 V, 0.5 ms impulse, 100kHz positive/negative oscillat- ing decay

Bellcore TR-TSY-000947

IEC-950, VDE EN 60950, EN 41003

CISPR 22, Class A

CE mark

24 Specifications