Figure 28 Equalize voltage and duration settings
TIMER
Switch # 1 2 3 4 5 6
OFF ON
1
2
VOLT
Switch # 1 | 2 | 3 |
10 sec. |
20 sec. |
38 sec. |
1.25 h |
0.6V
1.3V
1.9V
2.6V 1
3
4
5
6
Fuses
3.0 h |
5.0 h
LOP enabled
: switch in the ON position
3.2V
3.9V
4.6V
2
3
ON OFF
Table 37 Fuse
Designation | Capacity | Description |
|
|
|
ABS | 15 A | |
|
|
|
ABS ALM | 1/2 A | Alarm fuse for the above ABS fuse |
|
|
|
RC1 to RC24 | ||
|
|
|
CONV | 1/2 A | Protection for the internal converter in the controller |
|
|
|
METER | 1/2 A | Protection for the meter and selector panel if so equipped |
|
|
|
CHG | 1/2 A | Protection for internal circuitry of the controller when the CONT rotary switch |
|
| is in the CHG VOLT position |
|
|
|
Spare 1 and 2 | 0 to 5 A | For external loads as required (ex.: Helios Monitor) |
|
|
|
BAT | 1/2 A | Protection for internal circuitry of the controller when the CONT rotary switch |
|
| is in the BAT VOLT position |
|
|
|
CONT | Protection for the internal circuitry of the controller | |
|
|
|
Plus one unused position |
| |
|
|
|
Test points
Three sets of test points for applications as described in Table 38.
Table 38 Test points
Designation | Description |
|
|
CAL OUT + and - | To connect an external meter when calibrating the LED readout for current readings |
|
|
VOLT + and - | To connect an external meter when adjusting the BOD, LF, LV, HF, HV, HVSD, LVD and |
| LVR thresholds |
|
|
PWR EXT + and - | The connect an external power supply when adjusting the LVR threshold |
|
|
Operation 31