Figure 14 Front view of the (4)
CIRCUIT BREAKER PANEL |
| ||
| (4) | 1 | |
|
|
| |
FA |
|
|
|
REL | ( ) | SER NO ( | ) |
|
|
| 2 |
|
|
| 3 |
|
|
| 4 |
900A MAX. PANEL CAPACITY
|
|
|
|
|
|
| UNIT | 1 | 2 | 3 | 4 |
| AMPS | 225 | 225 | 225 | 225 |
| LOAD |
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The DC output connections can accommodate two 4/0 cables back to back for each circuit breaker. The required lugs can be either for two 3/8” holes at 1”
Refer to Table 21 for the maximum panel capacity.
Table 18 Circuit breaker sizes available for the (4)
Nominal current | CPC |
|
|
70 A (no shunt) | A0617079 |
|
|
70 A (with shunt) | A0617080 |
|
|
70 A (with relay trip) | A0617081 |
|
|
100 A (no shunt) | A0616667 |
|
|
100 A (with shunt) | A0616668 |
|
|
100 A (with relay trip) | A0616669 |
|
|
150 A (no shunt) | A0616670 |
|
|
150 A (with shunt) | A0616671 |
|
|
150 A (with relay trip) | A0616672 |
|
|
200 A (no shunt) | A0616673 |
|
|
200 A (with shunt) | A0616674 |
|
|
200 A (with relay trip) | A0616675 |
|
|
225 A (no shunt) | A0605489 |
|
|
225 A (with shunt) | A0605490 |
|
|
225 A (with relay trip) | A0605492 |
|
|
250 A (no shunt) | A0616676 |
|
|
250 A (with shunt) | A0616677 |
|
|
250 A (with relay trip) | A0616678 |
|
|
The (4)
•four breakers (70 to 225 A) mid trip with or without the metering shunt option (1 pole breakers)
•two breakers (70 to 225 A) mid trip with the relay trip option (takes a 2 pole space)
•two breakers (250 A) mid trip with or without the metering shunt option (takes a two pole breaker)
•one (250 A) breaker mid trip with the relay trip option (takes a 3 pole space)
Specifications 15