TROUBLESHOOTING

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

Shown in the drawing below are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

The suction line temperatures in Table 8 are based upon 80ºF dry bulb/67ºF wet bulb (50 percent R.H.) temperature and rated airflow across the evaporator during cooling cycle.

TABLE 9

INDOOR BLOWER PERFORMANCE

CFM AT 230 VOLTS

WA302, WA372

High Speed

Low Speed

FIGURE 9

FAN BLADE SETTING

AIRFLOW

TABLE 7

FAN BLADE DIMENSION

Model

Dimension A

 

 

WA302

1.25

WA372

 

"A"

MIS-1724

E.S.P.

 

 

 

 

In H2O

Dry Coil

Wet Coil

Dry Coil

Wet Coil

.0

1,395

1,315

950

935

 

 

 

 

 

.1

1,340

1,270

930

915

 

 

 

 

 

.2

1,285

1,190

910

885

 

 

 

 

 

.3

1,205

1,100

855

830

 

 

 

 

 

.4

1,110

1,000

800

755

 

 

 

 

 

.5

1,005

870

---

---

 

 

 

 

 

TABLE 10

RATED CFM AND ESP

REMOVAL OF FAN SHROUD

1.Disconnect all power to unit.

2.Remove the screws holding both grills – one on each side of unit – and remove grills.

3.Remove screws holding fan shroud to condenser and bottom – 9 screws.

4.Unwire condenser fan motor.

5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.

6.Service motor/fan as needed.

7.Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6 inches from compressor) as shown in Table 8.

TABLE 8

SUCTION LINE TEMPERATURES

 

Rated

95° F

82° F

Models

Airflow

OD Temp.

OD Temp.

 

 

 

 

WA302

1,000

56 – 59

64 – 66

 

 

 

 

WA372

1,100

57 – 59

62 – 64

 

1

1

 

Model

Rated

Rated

Recommended

CFM

ESP

Airflow Range

WA302

1,000

.40

930 – 1,300

 

 

 

 

WA371

1,100

.30

930 – 1,350

 

 

 

 

1Rated CFM and ESP on high speed tap

TABLE 11

MAXIMUM ESP OF OPERATION

ELECTRIC HEAT ONLY

Model

Front Outlet

Top Outlet

 

 

 

 

 

Speed

Low

High

Low

High

KW

Speed

Speed

Speed

Speed

 

 

 

 

 

A0Z

.50

.50

.50

.50

A05

.50

.50

.45

.50

A08

.50

.50

---

---

A10

.45

.50

.35

.50

A15

.35

.40

---

---

B0Z

.50

.50

.50

.50

B06

.40

.50

---

---

B09

.50

.50

.40

.45

B15

.30

.45

---

---

C0Z

.50

.50

.50

.50

C06

.50

.50

---

---

C09

.40

.50

.40

.45

C15

.35

.45

---

---

Manual

2100-404E

Page

17 of 19