The electrical data lists fuse and wire sizes (75ºC copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.

WIRING — LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TABLE 4

OPERATING VOLTAGE RANGE

TAP

RANGE

240V

253 – 216

 

 

208V

220 – 187

 

 

NOTE: The voltage should be measured a the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition.)

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 8.

LOW VOLTAGE CONNECTIONS

These units use a grounded 24 volt AC low voltage circuit.

The "R" terminal is the hot terminal and the "C" terminal is grounded.

"G" terminal is the fan input.

"Y" terminal is the compressor input for cooling.

"W1" terminal is the 1st stage electric heat. The reversing valve must be energized for heating mode.

"W2" terminal is second stage heat (if equipped).

"F" terminal is the ventilation input. This terminal energizes any factory installed ventilation option.

LOW VOLTAGE CONNECTIONS

FOR DDC CONTROL

Fan Only

Energize G

Cooling Mode

Energize Y, G

1st Stage Heating

Energize W1

2nd Stage Heating

Energize W1, W2

(if employed)

 

Ventilation

Energize G, F

TABLE 6

WALL THERMOSTAT

TABLE 5

THERMOSTAT WIRE SIZE

 

 

 

Maximum

Transformer

 

 

Distance

VA

FLA

Wire Gauge

In Feet

 

 

20 gauge

45

 

 

18 gauge

60

55

2.3

16 gauge

100

 

 

14 gauge

160

 

 

12 gauge

250

Thermostat

Predominate Features

 

 

8403-057

1 stage Cool, 1 stage Heat

Electronic Non-Programmable

TH5220D1153

Auto or Manual changeover

 

 

8403-058

2 stage Cool, 2 stage Heat

Electronic Non-Programmable

TH5220D1151

Auto or Manual changeover

 

 

 

3 stage Cool; 3 stage Heat

8403-060

Programmable/Non-Programmable Electronic

(1120-445)

HP or Conventional

 

Auto or Manual changeover

 

 

Manual

2100-404E

Page

9 of 19

Page 9
Image 9
Bard 2100-404E installation instructions Wiring LOW Voltage Wiring, LOW Voltage Connections, Operating Voltage Range

2100-404E specifications

The Bard 2100-404E is an advanced heating and cooling unit designed to provide efficient climate control solutions for various applications. This innovative model is renowned for its compact design and high performance, making it suitable for both residential and commercial settings.

One of the standout features of the Bard 2100-404E is its energy efficiency. It comes equipped with a high-efficiency compressor that not only helps in reducing energy consumption but also lowers operational costs. This model adheres to the latest energy efficiency standards, ensuring that users benefit from significant savings on their utility bills.

The unit utilizes environmentally friendly refrigerants, which contribute to its eco-friendly profile. By minimizing its carbon footprint, the Bard 2100-404E aligns with contemporary environmental standards and regulations, making it a responsible choice for conscientious consumers.

Another notable characteristic of the Bard 2100-404E is its robust construction and durability. The unit is built with high-quality materials designed to withstand harsh weather conditions, ensuring longevity and reliable performance over time. This makes it ideal for installation in various environments, including those subjected to extreme temperatures.

The Bard 2100-404E features a user-friendly digital control panel that allows for easy adjustments and monitoring of settings. Users can effortlessly customize their heating and cooling preferences, optimizing comfort within their spaces. The system also includes programmable settings, enhancing convenience and energy savings.

In terms of technologies, the Bard 2100-404E incorporates modern HVAC advancements such as variable speed fans and multi-zone capabilities. These features result in enhanced temperature control and improved indoor air quality, ensuring that every corner of a space is evenly conditioned.

Other characteristics include relatively low noise levels, making the unit suitable for installation in noise-sensitive areas. Additionally, the Bard 2100-404E is designed for easy maintenance, with accessible components that simplify servicing and repairs.

In conclusion, the Bard 2100-404E represents a smart investment for those seeking an efficient, durable, and versatile heating and cooling solution. With its energy-saving features, environmental consciousness, and cutting-edge technologies, it stands out as a premier choice for modern climate control needs.