Bard 2100-404E installation instructions Wiring - Low Voltage Wiring, Low Voltage Connections

Models: 2100-404E

1 19
Download 19 pages 30.55 Kb
Page 9
Image 9
WIRING — LOW VOLTAGE WIRING

The electrical data lists fuse and wire sizes (75ºC copper) for all models, including the most commonly used heater sizes. Also shown are the number of field power circuits required for the various models with heaters.

The unit rating plate lists a “Maximum Time Delay Relay Fuse” or “HACR Type” circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor motor.

The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect. To convert for the locking capability, bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out. This tab will now line up with the slot in the door. When shut, a padlock may be placed through the hole in the tab preventing entry.

WIRING — LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TABLE 4

OPERATING VOLTAGE RANGE

TAP

RANGE

240V

253 – 216

 

 

208V

220 – 187

 

 

NOTE: The voltage should be measured a the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition.)

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 8.

LOW VOLTAGE CONNECTIONS

These units use a grounded 24 volt AC low voltage circuit.

The "R" terminal is the hot terminal and the "C" terminal is grounded.

"G" terminal is the fan input.

"Y" terminal is the compressor input for cooling.

"W1" terminal is the 1st stage electric heat. The reversing valve must be energized for heating mode.

"W2" terminal is second stage heat (if equipped).

"F" terminal is the ventilation input. This terminal energizes any factory installed ventilation option.

LOW VOLTAGE CONNECTIONS

FOR DDC CONTROL

Fan Only

Energize G

Cooling Mode

Energize Y, G

1st Stage Heating

Energize W1

2nd Stage Heating

Energize W1, W2

(if employed)

 

Ventilation

Energize G, F

TABLE 6

WALL THERMOSTAT

TABLE 5

THERMOSTAT WIRE SIZE

 

 

 

Maximum

Transformer

 

 

Distance

VA

FLA

Wire Gauge

In Feet

 

 

20 gauge

45

 

 

18 gauge

60

55

2.3

16 gauge

100

 

 

14 gauge

160

 

 

12 gauge

250

Thermostat

Predominate Features

 

 

8403-057

1 stage Cool, 1 stage Heat

Electronic Non-Programmable

TH5220D1153

Auto or Manual changeover

 

 

8403-058

2 stage Cool, 2 stage Heat

Electronic Non-Programmable

TH5220D1151

Auto or Manual changeover

 

 

 

3 stage Cool; 3 stage Heat

8403-060

Programmable/Non-Programmable Electronic

(1120-445)

HP or Conventional

 

Auto or Manual changeover

 

 

Manual

2100-404E

Page

9 of 19

Page 9
Image 9