Bard CH4S1 Table Indoor Blower Performance, table MAXIMUM ESP OF OPERATION, Manual, 2100-455M

Models: CH3S1 CH5S1 CH4S1

1 28
Download 28 pages 36.1 Kb
Page 24
Image 24
TABLE 6

TABLE 6

INDOOR BLOWER PERFORMANCE

Model

Rated

j

k

l

m

Electric Heat

Max

2nd Stage Cooling

1st Stage Cooling

Blower Only

ESP

 

ESP

2nd Stage Heating

1st Stage Heating

or Vent Mode

 

 

 

 

CH3S1

.15

0.5

1100

800

500

1100

CH4S1

.2

0.5

1500

1100

500

1700

CH5S1

.2

0.5

1700

1300

500

1700

 

 

 

 

 

 

 

NOTE: These units are equipped with a variable speed (ECM) indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating and cooling, dry and wet coil conditions and at both 230/208 or 460 volts.

Maximum ESP (inches WC) shown is with 2" thick disposable filter.

Rated CFM for 2nd Stage Operation – required for maximum performance rating.

1st Stage – the CFM output on 1st Stage Heating or Cooling.

Blower only CFM is the total air being circulated during continuous fan mode.

table 7

MAXIMUM ESP OF OPERATION

All

High Speed

.5

Manual

2100-455M

Page

24 of 28

Page 24
Image 24
Bard CH4S1, CH5S1, CH3S1 Table Indoor Blower Performance, table MAXIMUM ESP OF OPERATION, Manual, 2100-455M, Page, 24 of