TABLE 8
PRESSURE TABLE
HIGH CAPACITY COOLING |
| AIR TEMPERATURE ENTERING OUTDOOR COIL DEGREE F |
|
| ||||||||
MODEL | RETURN AIR | PRESSURE | 75°F | 80°F | 85°F | 90°F | 95°F | 100°F | 105°F | 110°F | 115°F | |
TEMPERATURE | ||||||||||||
|
|
|
|
|
|
|
|
|
|
| ||
| 75° DB | LOW SIDE | 134 | 134 | 134 | 135 | 137 | 138 | 140 | 143 | 146 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 62° WB | HIGH SIDE | 298 | 318 | 339 | 363 | 388 | 415 | 445 | 476 | 510 | |
|
|
|
|
|
|
|
|
|
|
|
| |
CH3S1 | 80° DB | LOW SIDE | 143 | 143 | 143 | 144 | 152 | 148 | 150 | 153 | 156 | |
|
|
|
|
|
|
|
|
|
|
| ||
67° WB | HIGH SIDE | 306 | 326 | 348 | 372 | 402 | 426 | 456 | 488 | 523 | ||
| ||||||||||||
| 85° DB | LOW SIDE | 148 | 148 | 148 | 149 | 151 | 153 | 155 | 158 | 161 | |
| 72° WB | HIGH SIDE | 317 | 337 | 360 | 385 | 412 | 441 | 472 | 505 | 541 | |
| 75° DB | LOW SIDE | 131 | 133 | 135 | 137 | 138 | 139 | 139 | 140 | 140 | |
| 62° WB | HIGH SIDE | 308 | 332 | 356 | 380 | 406 | 431 | 456 | 483 | 509 | |
CH4S1 | 80° DB | LOW SIDE | 140 | 142 | 144 | 146 | 147 | 149 | 149 | 150 | 150 | |
67° WB | HIGH SIDE | 316 | 340 | 365 | 390 | 416 | 442 | 468 | 495 | 522 | ||
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
| 85° DB | LOW SIDE | 145 | 147 | 149 | 151 | 153 | 154 | 154 | 155 | 155 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 72° WB | HIGH SIDE | 327 | 352 | 378 | 404 | 431 | 457 | 484 | 512 | 540 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 75° DB | LOW SIDE | 130 | 131 | 131 | 132 | 134 | 135 | 137 | 138 | 140 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 62° WB | HIGH SIDE | 336 | 359 | 381 | 406 | 430 | 455 | 482 | 510 | 538 | |
|
|
|
|
|
|
|
|
|
|
|
| |
CH5S1 | 80° DB | LOW SIDE | 139 | 140 | 140 | 141 | 143 | 144 | 146 | 148 | 150 | |
|
|
|
|
|
|
|
|
|
|
| ||
67° WB | HIGH SIDE | 345 | 368 | 391 | 416 | 441 | 467 | 494 | 523 | 552 | ||
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
| 85° DB | LOW SIDE | 144 | 145 | 145 | 146 | 148 | 149 | 151 | 153 | 155 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 72° WB | HIGH SIDE | 357 | 381 | 405 | 431 | 456 | 483 | 511 | 541 | 571 | |
|
|
|
|
|
|
|
|
|
|
|
|
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.
TABLE 9
PRESSURE TABLE
LOW CAPACITY COOLING |
| AIR TEMPERATURE ENTERING OUTDOOR COIL DEGREE F |
|
| ||||||||
MODEL | RETURN AIR | PRESSURE | 75°F | 80°F | 85°F | 90°F | 95°F | 100°F | 105°F | 110°F | 115°F | |
TEMPERATURE | ||||||||||||
|
|
|
|
|
|
|
|
|
|
| ||
| 75° DB | LOW SIDE | 139 | 140 | 141 | 142 | 143 | 145 | 147 | 149 | 151 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 62° WB | HIGH SIDE | 259 | 284 | 308 | 333 | 359 | 385 | 410 | 438 | 464 | |
|
|
|
|
|
|
|
|
|
|
|
| |
CH3S1 | 80° DB | LOW SIDE | 149 | 150 | 151 | 152 | 157 | 155 | 157 | 159 | 161 | |
|
|
|
|
|
|
|
|
|
|
| ||
67° WB | HIGH SIDE | 266 | 291 | 316 | 342 | 370 | 395 | 421 | 449 | 476 | ||
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
| 85° DB | LOW SIDE | 154 | 155 | 156 | 157 | 158 | 160 | 162 | 165 | 167 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 72° WB | HIGH SIDE | 275 | 301 | 327 | 354 | 381 | 409 | 436 | 465 | 493 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 75° DB | LOW SIDE | 137 | 137 | 139 | 140 | 141 | 143 | 144 | 146 | 147 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 62° WB | HIGH SIDE | 281 | 301 | 323 | 345 | 370 | 394 | 419 | 447 | 475 | |
|
|
|
|
|
|
|
|
|
|
|
| |
CH4S1 | 80° DB | LOW SIDE | 146 | 147 | 149 | 150 | 151 | 153 | 154 | 156 | 157 | |
|
|
|
|
|
|
|
|
|
|
| ||
67° WB | HIGH SIDE | 288 | 309 | 331 | 354 | 379 | 404 | 430 | 458 | 487 | ||
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
| 85° DB | LOW SIDE | 151 | 152 | 154 | 155 | 156 | 158 | 159 | 161 | 162 | |
|
|
|
|
|
|
|
|
|
|
|
| |
| 72° WB | HIGH SIDE | 298 | 320 | 343 | 366 | 392 | 418 | 445 | 474 | 504 | |
| 75° DB | LOW SIDE | 136 | 137 | 139 | 141 | 142 | 143 | 144 | 145 | 145 | |
| 62° WB | HIGH SIDE | 293 | 316 | 340 | 364 | 389 | 413 | 439 | 464 | 489 | |
CH5S1 | 80° DB | LOW SIDE | 145 | 147 | 149 | 151 | 150 | 153 | 154 | 155 | 155 | |
67° WB | HIGH SIDE | 300 | 324 | 349 | 373 | 391 | 424 | 450 | 476 | 502 | ||
| ||||||||||||
| 85° DB | LOW SIDE | 150 | 152 | 154 | 156 | 157 | 158 | 159 | 160 | 160 | |
| 72° WB | HIGH SIDE | 311 | 335 | 361 | 386 | 413 | 439 | 466 | 493 | 520 |
Low side pressure ± 2 PSIG
High side pressure ± 5 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the system, the charge should be removed, system evacuated and recharged to serial plate instruction.
Manual
Page | 25 of 28 |