Bard PA13241-A Wiring - Main Power, WIRING - 24V LOW VOLTAGE CONTROL CIRCUIT, Transformer Taps

Models: PA13361-B PA13301-A PA13241-A PA13361-A

1 25
Download 25 pages 63.7 Kb
Page 13
Image 13
WIRING – MAIN POWER

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. If field installed heaters are added to the basic unit, a second separate power supply circuit will be required. The heater rating plate located adjacent to the basic unit rating plate will show the appropriate circuit ampacity fuse size, etc. (Also see “Electrical Specifications” on pages 5 & 7.) All models are suitable for connection with copper wire only. These instructions must be adhered to. Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material.

The electrical specifications list fuse and wire sizes (75°F copper) for all models including the most commonly used heater sizes.

The unit rating plate lists a “Maximum Time Delay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor.

WIRING – 24V LOW VOLTAGE CONTROL CIRCUIT

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 6.

TABLE 6

THERMOSTAT WIRE SIZE

 

 

 

Maximum

 

 

 

Distance

Transformer VA

FLA

Wire Gauge

In Feet

 

 

 

 

 

 

20

45

 

 

18

60

55

2.3

16

100

 

 

14

160

 

 

12

250

 

 

 

 

TRANSFORMER TAPS

230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

THERMOSTATS

See specific wiring information for the different models, heater KWs, and voltages on unit and heating wiring diagrams.

 

TABLE 7

 

WALL THERMOSTATS

 

 

Thermostat

Predominant Features

 

 

8403-057

1 stage Cool; 1 stage Heat

heat-off-cool Fan: on-auto

(TH3110D1040)

Electronic Non-Programmable

 

 

8403-058

2 stage Cool; 2 stage Heat

Electronic Non-Programmable

(TH5220D1151)

 

Auto or Manual changeover

 

3 stage Cool; 3 stage Heat

8403-060

Programmable/Non-Programmable Electronic

(1120-445)

HP or Conventional

 

Auto or Manual changeover

 

 

IMPORTANT NOTE: Only the thermostats as shown above will work with this equipment. The thermostats and correct operation can be assured only by proper selection and application of these parts.

Manual

2100-467D

Page

13 of 25

Page 13
Image 13
Bard PA13241-A Wiring - Main Power, WIRING - 24V LOW VOLTAGE CONTROL CIRCUIT, Transformer Taps, Thermostats, Range, Manual