TABLE 4
OPTIONAL FIELD INSTALLED ELECTRIC HEATER TABLE
|
| Htr. KW & Capacity | Htr. KW & Capacity |
|
|
|
| Circuit B |
|
| |||
|
| @ 240 Volts | @ 208 Volts |
| Heater |
|
|
|
| ||||
Heater |
| 240/208V |
|
|
|
|
| ||||||
Unit Volts |
|
|
|
| Internal |
|
|
|
|
| |||
Package |
|
|
|
| Htr. |
| 3 | 1 | 2 | 2 | |||
Phases |
|
|
|
| Circuit |
| |||||||
|
|
|
| No. Field | Min. | Max. Over | Field |
| |||||
Model No. | KW | BTUH | KW | BTUH | Amps |
| |||||||
| Breaker | Circuits | Circuit | Current | Power | Ground | |||||||
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
| Ampacity | Protection | Wiring | Wire Size | |
|
|
|
|
|
|
|
|
|
|
|
|
| |
5 | 17,100 | 3.75 | 12,800 | 20.8/18.1 |
| 1 | 26/23 | 30/25 | 10/10 | 10 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
10 | 34,100 | 7.50 | 26,000 | 41.6/36.2 | 30/60 | 1 | 53/46 | 60/50 | 6/8 | 10 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
15 | 51,200 | 11.25 | 38,400 | 62.5/54.1 |
| 1 | 79/68 | 80/70 | 4/4 | 8 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
5 | 17,100 | 3.75 | 12,800 | 20.8/18.1 |
| 1 | 26/23 | 30/25 | 10/10 | 10 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
10 | 34,100 | 7.50 | 26,000 | 41.6/36.2 | 30/60 | 1 | 53/46 | 60/50 | 6/8 | 10 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
15 | 51,200 | 11.25 | 38,400 | 62.5/54.1 |
| 1 | 79/68 | 80/70 | 4/4 | 8 | |||
|
|
|
|
|
|
|
|
|
|
|
|
| |
9 | 30,700 | 6.75 | 23,000 | 21.7/18.7 | None | 1 | 28/24 | 30/25 | 10/10 | 10 | |||
|
|
|
|
|
|
|
|
|
|
|
| ||
15 | 51,200 | 11.25 | 38,400 | 36.2/31.2 | 1 | 46/39 | 50/40 | 8/8 | 10 | ||||
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
9 | 30,700 | 6.75 | 23,000 | 21.7/18.7 | None | 1 | 28/24 | 30/25 | 10/10 | 10 | |||
|
|
|
|
|
|
|
|
|
|
|
| ||
15 | 51,200 | 11.25 | 38,400 | 36.2/31.2 | 1 | 46/39 | 50/40 | 8/8 | 10 | ||||
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
9 | 30,700 |
|
| 10.8 | None | 1 | 14 | 15 | 14 | 14 | |||
|
|
|
|
|
|
|
|
|
|
|
| ||
15 | 51,200 |
|
| 18 | 1 | 28 | 30 | 10 | 12 | ||||
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
1 Maximum size of the time delay fuse or HACR circuit breaker for protection of field wiring devices.
2 Based on wire suitable for 75°C. Other wiring materials must be rated for marked “Minimum Circuit Ampacity” or greater. Based on 75°C copper wire. All wiring must conform to the National Electric Code and all local codes.
3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for power conductor sizing.
IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all existing local codes.