TABLE 4

OPTIONAL FIELD INSTALLED ELECTRIC HEATER TABLE

 

 

Htr. KW & Capacity

Htr. KW & Capacity

 

 

 

 

Circuit B

 

 

 

 

@ 240 Volts

@ 208 Volts

 

Heater

 

 

 

 

Heater

 

240/208V

 

 

 

 

 

Unit Volts

 

 

 

 

Internal

 

 

 

 

 

Package

 

 

 

 

Htr.

 

3

1

2

2

Phases

 

 

 

 

Circuit

 

 

 

 

 

No. Field

Min.

Max. Over

Field

 

Model No.

KW

BTUH

KW

BTUH

Amps

 

 

Breaker

Circuits

Circuit

Current

Power

Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ampacity

Protection

Wiring

Wire Size

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-A05

240/208-1

5

17,100

3.75

12,800

20.8/18.1

 

1

26/23

30/25

10/10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-A10

240/208-1

10

34,100

7.50

26,000

41.6/36.2

30/60

1

53/46

60/50

6/8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-A15

240/208-1

15

51,200

11.25

38,400

62.5/54.1

 

1

79/68

80/70

4/4

8

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-A05

240/208-1

5

17,100

3.75

12,800

20.8/18.1

 

1

26/23

30/25

10/10

10

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-A10

240/208-1

10

34,100

7.50

26,000

41.6/36.2

30/60

1

53/46

60/50

6/8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-A15

240/208-1

15

51,200

11.25

38,400

62.5/54.1

 

1

79/68

80/70

4/4

8

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-B09

240/208-3

9

30,700

6.75

23,000

21.7/18.7

None

1

28/24

30/25

10/10

10

 

 

 

 

 

 

 

 

 

 

 

 

EHP313-B15

240/208-3

15

51,200

11.25

38,400

36.2/31.2

1

46/39

50/40

8/8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-B09

240/208-3

9

30,700

6.75

23,000

21.7/18.7

None

1

28/24

30/25

10/10

10

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-B15

240/208-3

15

51,200

11.25

38,400

36.2/31.2

1

46/39

50/40

8/8

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-C09

480-3

9

30,700

 

 

10.8

None

1

14

15

14

14

 

 

 

 

 

 

 

 

 

 

 

 

EHP513-C15

480-3

15

51,200

 

 

18

1

28

30

10

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Maximum size of the time delay fuse or HACR circuit breaker for protection of field wiring devices.

2 Based on wire suitable for 75°C. Other wiring materials must be rated for marked “Minimum Circuit Ampacity” or greater. Based on 75°C copper wire. All wiring must conform to the National Electric Code and all local codes.

3 These “Minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), Article 310 for power conductor sizing.

IMPORTANT: While this electrical data is presented as a guide, it is important to electrically connect properly sized fuses and conductor wires in accordance with the National Electrical Code and all existing local codes.