Bard PA13361-B 19 of, 2100-467D, Table Pressure Table, Continued on Page 20 in Table

Models: PA13361-B PA13301-A PA13241-A PA13361-A

1 25
Download 25 pages 63.7 Kb
Page 19
Image 19
19 of 25

Page

Manual

19 of 25

2100-467D

TABLE 10

PRESSURE TABLE

COOLING

 

 

 

 

 

 

 

 

 

Air Temperature Entering Outdoor Coil Degree F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return Air

Pressure

65°

70°

75°

80°

85°

90°

95°

100°

105°

110°

115°

120°

125°

 

Model

Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75° DB

Low Side

125

127

129

131

133

135

137

138

140

142

143

145

147

 

 

62° WB

High Side

238

262

286

310

334

358

382

407

432

457

482

507

532

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PA1324

80° DB

Low Side

134

136

138

140

142

144

146

148

150

151

153

155

157

 

67° WB

High Side

244

269

293

318

343

367

392

418

443

469

494

520

546

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85° DB

Low Side

144

146

148

151

153

155

157

159

161

163

165

167

169

 

 

72° WB

High Side

253

278

304

329

355

380

406

432

459

485

512

538

565

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75° DB

Low Side

126

128

131

133

135

137

139

141

143

145

148

150

152

 

 

62° WB

High Side

246

267

289

310

332

353

374

402

429

457

484

512

539

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PA1330

80° DB

Low Side

135

137

140

142

144

147

149

151

153

156

158

160

162

 

67° WB

High Side

252

274

296

318

340

362

384

412

440

469

497

525

553

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85° DB

Low Side

145

148

150

153

155

158

160

163

165

167

170

172

174

 

 

72° WB

High Side

261

284

306

329

352

375

397

427

456

485

514

543

573

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

75° DB

Low Side

125

127

128

130

132

133

135

136

138

139

141

142

 

 

 

62° WB

High Side

247

271

295

320

344

369

393

418

443

468

494

519

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PA1336

80° DB

Low Side

134

136

137

139

141

142

144

146

147

149

150

152

 

 

67° WB

High Side

253

278

303

328

353

378

403

429

455

480

506

532

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85° DB

Low Side

144

146

148

149

151

153

155

157

158

160

162

163

 

 

 

72° WB

High Side

262

288

314

339

365

391

417

444

471

497

524

551

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW SIDE PRESSURE +2 PSIG

HIGH SIDE PRESSURE +5 PSIG

Tables based upon rated CFM (airflow) across the evaporator coil.

If incorrect charge suspected (more than +2 psig suction, +5 psig liquid),

it is recommended refrigerant charge be reclaimed, system evacuated and charged to serial plate quantity.

(Continued on Page 20 in Table 11)