LOW VOLTAGE CONNECTIONS

These units use a grounded 24 volt AC low voltage
circuit.
The “R” terminal is the hot terminal and the “C”
terminal is grounded.
“G” terminal or pins 6 and 1 of P2 are the fan inputs.
Both must be energized for proper fan operation. This
is done automatically in the factory installed climate
control options. If the climate control option is
abandoned and connections are made directly to P2 both
pins 6 and 1 of P2 must be energized for proper
operation.
“Y” terminal or pin 7 of P2 is the compressor input.
“B” terminal or pin 8 of P2 is the reversing valve input.
The reversing valve must be energized for heating
mode.
“R” terminal or pin 10 of P2 is 24 VAC hot.
“C” terminal or pin 11 of P2 is 24 VAC grounded.
“L” terminal or pin 12 of P2 is compressor lockout

output

. This terminal is activated on a high or low
pressure trip by the electronic heat pump control. This
is a 24 VAC output.
“W2” terminal or pin 9 of P2 is second stage heat (if
equipped). If the unit is equipped with an optional hot
water coil plenum box or electric heat these will be
energized by this terminal.
“O1” terminal of pin 5 of P2 is the ventilation input.
This terminal energizes any factory installed ventilation
option.
“E” terminal or pin 3 of P2 is the emergency heat input.
This terminal energizes the emergency heat relay.
ROFSNOITCENNOCEGATLOVWOL LORTNOCCDD
ylnOnaFGezigrenE
edoMgnilooCG,YezigrenE
gnitaeHpmuPtaeHB,G,YezigrenE
gnitaeHegatSdn2 )deyolpmefi( 2W,GezigrenE
noitalitneV1O,GezigrenE
taeHycnegremEE,2W,BezigrenE

GENERAL

This unit is equipped with a variable speed ECM motor.
The motor is designed to maintain rated airflow up to
the maximum static allowed. It is important that the
blower motor plugs are not plugged in or unplugged
while the power is on. Failure to remove power prior
to unplugging or plugging in the motor could result in
motor failure.
CAUTION
Do not plug in or unplug blower motor
connectors while the power is on. Failure to do
so may result in motor failure.
NOTE: For total and proper control using DDC, a total
of 6 controlled outputs are required (5 if no
ventilation system is installed). For proper
system operation under Emergency Heat
conditions. Where the compressor needs to be
deactivated, the B-W2-E outputs need to be
energized. Removing the Y (compressor) signal
alone turns the compressor off, but does not
activate the additional circuitry embedded in
the heat pump for proper and complete
operation.