TROUBLESHOOTING

TROUBLESHOOTING

FAN BLADE SETTING DIMENSIONS

REFRIGERANT CHARGE

Shown in Figure 10 is the correct fan blade setting dimension for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be checked and blade adjusted in or out on the motor shaft accordingly.

FIGURE 10

TABLE 5

 

Dimension

Model

A

 

 

WA602N

1.75

 

 

REMOVAL OF FAN SHROUD

1.Disconnect all power to the unit.

2.Remove the screws holding both grilles, one on each side of unit, and remove grilles.

3.Remove screws holding fan shroud to condenser and bottom. Nine (9) screws.

4.Unwire condenser fan motor.

5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.

6.Service motor/fan as needed.

7.Reverse steps to reinstall.

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature (6” from compressor) as shown in Table 7.

TABLE 7

REFRIGERANT CHARGE

 

Rated

95 OD

82 OD

Model

Airflow

Temperature

Temperature

 

 

 

 

WA602

1700

53 - 55

60 - 62

 

 

 

 

WA482

1550

54 - 56

65 - 67

 

 

 

 

The suction line temperatures in table above are based upon 80° F dry bulb / 67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle.

TABLE 8

RATED CFM AND ESP

 

Rated

 

Recommended

Model

CFM

ESP

Airflow Range

 

 

 

 

 

 

WA602N

1425

0.20

1775 - 1425

j

 

 

 

 

 

WA6023

1425

0.20

1775 - 1425

j

 

 

 

 

 

WA6022

1525

0.20

1850 - 1525

k

 

 

 

 

 

WA4823

1350

0.20

1600 - 1350

j

 

 

 

 

 

WA4822

1400

0.20

1700 - 1400

k

 

 

 

 

 

jRated CFM & ESP on High Speed tap with 14 x 28 return air filter grille

kRated CFM & ESP on High Speed tap with 20 x 30 filter

TABLE 6

INDOOR BLOWER PERFORMANCE

CFM @ 230V

 

 

WA602N

 

 

 

 

 

 

 

 

 

WA6023

WA6022

WA4823

WA4822

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Speed

High Speed

High Speed

High Speed

 

 

E.S.P.

 

 

 

 

 

 

 

 

 

 

Dry

Wet

Dry

Wet

Dry

Wet

Dry

Wet

 

 

In H2O

Coil

Coil

Coil

Coil

Coil

Coil

Coil

Coil

 

 

.0

1775

1600

1850

1675

1600

1525

1700

1625

 

 

.1

1675

1525

1755

1600-

1525

1425

1600

1525

 

 

.2

1575

1425

1700

1525

1425

1350

1475

1400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual 2100-348 Page 17