Bard WA6022, WA6023, WA602N, WA4823, WA4822 installation instructions Table Electrical Specifications

Models: WA4822 WA4823 WA6022 WA602N WA6023

1 21
Download 21 pages 61.19 Kb
Page 7
Image 7
TABLE 2

Page

Manual

5

2100-348

 

TABLE 2

ELECTRICAL SPECIFICATIONS

SINGLE CIRCUIT

DUAL CIRCUIT

 

 

 

3

1

2

2

3

1

2

2

 

 

 

 

Maximum

 

 

Minimum

Maximum

 

 

 

 

 

 

No.

 

 

 

External Fuse

 

 

 

 

 

 

 

External

Field

 

Circuit

or

Field Power

Ground

 

Rated

Field

Minimum

Fuse or

Power

Ground

Ampacity

Ckt. Breaker

Wire Size

Wire Size

 

Volts &

Power

Circuit

Ckt.

Wire

Wire

 

 

 

 

 

 

 

 

 

CKT A

CKT B

CKT A

CKT B

CKT A

CKT B

CKT A

CKT B

Model

Phase

Circuits

Ampacity

Breaker

Size

Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA4822A00, A0Z

230/208-1

1

38

50

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA4822B00, B0Z

230/208-3

1

26

35

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA4823A00, A0Z

230/208-1

1

38

50

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA4823B00, B0Z

230/208-3

1

26

35

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WA6022A00, A0Z

 

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A05

230/208-1

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A10

 

1

55

60

6

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WA6022B00, B0Z

230/208-3

1

32

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

B09

1

34

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WA6023A00, A0Z

 

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A05

230/208-1

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A10

 

1

55

60

6

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WA6023B00, B0Z

230/208-3

1

32

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

B09

1

34

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WA602NA00, A0Z

 

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A05

230/208-1

1

44

60

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

A10

 

1

55

60

6

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

WA602NB00, B0Z

230/208-3

1

32

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

B09

1

34

45

8

10

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

jMaximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.

kBased on 75° C copper wire. All Wiring must conform to NEC and all local codes.

lThese “minimum Circuit Ampacity” values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest revision), article 310 for power conductor sizing. CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to note 8 of table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.

Page 7