Bard WA721, WA702-A, WA611, WA701-C, WA701-B installation instructions Electrical Specifications

Models: WA701-C WA701-B WA611 WA721 WA702-A

1 26
Download 26 pages 43.51 Kb
Page 6
Image 6

Page

Manual

4

2100-425

TABLE 3

ELECTRICAL SPECIFICATIONS

SINGLE CIRCUIT

DUAL CIRCUIT

 

 

 

3

1

2

2

 

3

 

1

 

2

 

2

 

 

 

 

Maximum

 

 

Minimum Circuit

Maximum Over

 

 

 

 

 

 

 

 

No. of

Minimum

Field

Ground

Current

Field Wire Size

Ground Wire Size

 

 

Over

Ampacity

Protection

 

 

Power

Circuit

Current

Wire

Wire

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MODELS

Rated

Circuits

Ampacity

Protection

Size

Size

CKT A

 

CKT B

CKT A

 

CKT B

CKT A

 

CKT B

CKT A

 

CKT B

WA611-A00,A0Z

 

1

43

50

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-A05

203/208-1

1

43

50

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-A08

1

47

60

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

 

 

 

 

 

-A10

 

1

58

60

6

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

WA611-B00,B0Z

230/208-3

1

29

45

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-B09

1

33

45

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

 

 

 

 

 

WA611-C00, C0Z

460-3

1

15

20

12

12

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-C09

1

17

20

12

12

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

 

 

 

 

 

WA702-A00,A0Z

 

1

48

60

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-A05

 

1

48

60

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-A10

203/208-1

1

59

60

6

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-A15

 

1 or 2

85

90

4

8

59

 

26

60

 

30

6

 

10

10

 

10

-A20

 

1 or 2

110

110

2

6

59

 

52

60

 

60

6

 

6

10

 

10

WA701-B00,B0Z

 

1

36

50

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-B09

230/208-3

1

36

50

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-B15

1

52

60

6

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

 

 

 

 

 

-B18

 

1

60

60

6

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

WA701-C00,C0Z

 

1

17

25

12

12

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-C09

460-3

1

17

25

12

12

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-C15

 

1

26

30

10

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

WA721-B00,B0Z

 

1

36

50

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-B09

230/208-3

1

36

50

8

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-B15

1

52

60

6

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

 

 

 

 

 

-B18

 

1

60

60

6

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

WA721-C00,C0Z

 

1

17

25

12

12

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-C09

460-3

1

17

25

12

12

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

-C15

 

1

26

30

10

10

NA

 

NA

NA

 

NA

NA

 

NA

NA

 

NA

jMaximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors. k Based on 75°C copper wire. All wiring must conform to the National Electric Code (NEC) and all local codes.

l These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electric Code (latest version), Article 310 for power conductor sizing. CAUTION: When more than one filed power conductor circuit is run through one conduit, the conductors must be derated. Pay special attention to Note * of Table 310 regarding Ampacity Adjustment Factors when more than 3 conductors are in a raceway.

Page 6
Image 6
Bard WA721, WA702-A, WA611, WA701-C, WA701-B installation instructions Electrical Specifications