FAN BLADE SETTING DIMENSIONS
Shown in the drawing below are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be check and blade adjusted in or out on the motor shaft accordingly.
FIGURE 11
TABLE 6
Model | Dimension | |
A | ||
| ||
|
| |
WH183 | 1.00 | |
WH242 | ||
| ||
|
|
REMOVAL OF THE FAN SHROUD
1.Disconnect all power to unit.
2.Remove the screws holding both grilles, one on each side of unit, and remove grilles.
3.Remove screws (9) holding fan shroud to condenser and bottom.
4.Unwire condenser fan motor.
5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.
6.Service motor/fan as needed.
7.Reverse steps to reinstall.
REFRIGERANT CHARGE
The correct system
(6” from compressor) as shown in Table 7.
TABLE 7
(Temperatures °F)
| Rated | 95o OD | 82o OD | ||||
Model | Airflow | Temperature | Temperature | ||||
|
|
|
|
|
|
|
|
WH183 | 650 | 56 | - | 58 | 63 | - | 65 |
WH242 | 800 | 57 | - | 59 | 65 | - | 67 |
|
|
|
|
|
|
|
|
The suction line temperatures in Table 7 are based upon 80° F dry bulb/67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle.
TABLE 8
INDOOR BLOWER PERFORMANCE
CFM @ 230V
E.S.P. | WH183, | |||
WH242 | ||||
In H2O |
|
|
| |
Dry | / | Wet | ||
| ||||
|
|
|
| |
.0 | 1020 | / | 975 | |
.1 | 960 | / | 905 | |
.2 | 865 | / | 800 | |
.3 | 820 | / | 735 | |
.4 | 735 | / | 650 | |
.5 | 615 | / | 535 | |
.6 | - - | / | - - | |
|
|
|
|
TABLE 9
Model | Rated | Rated | Recommended | |||
CFM * | ESP * | Airflow Range | ||||
| ||||||
|
|
|
|
|
| |
WH183 | 650 | .40 | 575 | 725 | ||
|
|
|
|
|
| |
WH242 | 800 | .20 | 700 | 950 | ||
|
|
|
|
|
|
* Rated CFM and ESP on high speed tap.
TABLE 10
MAXIMUM ESP OF OPERATION
Model |
| ESP | |
|
|
| |
WH183 | A00 | .50 | |
A04 | .50 | ||
WH242 | |||
A08 | .40 | ||
| |||
|
|
| |
WH242 | B00 | .50 | |
B06 | .50 | ||
| |||
|
|
| |
WH242 | C00 | .50 | |
C06 | .50 | ||
| |||
|
|
|
Values shown are for units equipped with standard throwaway filter or 1” washable filter. Derate ESP by .15 for 2” pleated filter.
Manual
Page 17