FAN BLADE SETTING DIMENSIONS

FAN BLADE SETTING DIMENSIONS

Shown in the drawing below are the correct fan blade setting dimensions for proper air delivery across the outdoor coil.

Any service work requiring removal or adjustment in the fan and/or motor area will require that the dimensions below be check and blade adjusted in or out on the motor shaft accordingly.

FIGURE 11

TABLE 6

Model

Dimension

A

 

 

 

WH183

1.00

WH242

 

 

 

REMOVAL OF THE FAN SHROUD

1.Disconnect all power to unit.

2.Remove the screws holding both grilles, one on each side of unit, and remove grilles.

3.Remove screws (9) holding fan shroud to condenser and bottom.

4.Unwire condenser fan motor.

5.Slide complete motor, fan blade, and shroud assembly out the left side of the unit.

6.Service motor/fan as needed.

7.Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit rating plate. Optimum unit performance will occur with a refrigerant charge resulting in a suction line temperature

(6” from compressor) as shown in Table 7.

TABLE 7

(Temperatures °F)

 

Rated

95o OD

82o OD

Model

Airflow

Temperature

Temperature

 

 

 

 

 

 

 

 

WH183

650

56

-

58

63

-

65

WH242

800

57

-

59

65

-

67

 

 

 

 

 

 

 

 

The suction line temperatures in Table 7 are based upon 80° F dry bulb/67° F wet bulb (50% R.H.) temperature and rated airflow across the evaporator during cooling cycle.

TABLE 8

INDOOR BLOWER PERFORMANCE

CFM @ 230V

E.S.P.

WH183,

WH242

In H2O

 

 

 

Dry

/

Wet

 

 

 

 

 

.0

1020

/

975

.1

960

/

905

.2

865

/

800

.3

820

/

735

.4

735

/

650

.5

615

/

535

.6

- -

/

- -

 

 

 

 

TABLE 9

Model

Rated

Rated

Recommended

CFM *

ESP *

Airflow Range

 

 

 

 

 

 

 

WH183

650

.40

575

---

725

 

 

 

 

 

 

WH242

800

.20

700

---

950

 

 

 

 

 

 

* Rated CFM and ESP on high speed tap.

TABLE 10

MAXIMUM ESP OF OPERATION

Model

 

ESP

 

 

 

WH183

A00

.50

A04

.50

WH242

A08

.40

 

 

 

 

WH242

B00

.50

B06

.50

 

 

 

 

WH242

C00

.50

C06

.50

 

 

 

 

Values shown are for units equipped with standard throwaway filter or 1” washable filter. Derate ESP by .15 for 2” pleated filter.