To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non alkaline. The recommended products for cleaning are:

SENTINEL X300 or X400 and FERNOX heating circuit restore. Please ensure to use this product proceeding strictly in accordance with the manufacturers instructions. Finally fill the system with the correct strength of central heating inhibitor.

2.2. Existing system

Before proceeding with installation of the boiler, the system must be cleaned and flushed out to remove sludge and contaminants, using suitable proprietary products as described in section 2.1.

To avoid damaging metal, plastic and rubber parts, use only neutral cleaners, i.e. non-acid and non- alkaline such us SENTINEL X100 and FERNOX heating circuit protective. To use this product proceeding strictly in accordance with the maker’s directions.

Remember that the presence of foreign matter in the heating system can adversely affect the operation of the boiler (e.g. overheating and noisy operation of the heat exchanger). Dose with inhibitor.

Failure to observe the above will render the guarantee null and void.

10. BOILER INSTALLATION

Decide upon the boiler location, then tape the template on the wall.

Connect the pipework to the gas and water inlets prearranged on the template lower bar.

If you are either installing the boiler on a pre-existing system or replacing it, we suggest you also fit strainers on the system return pipework to the boiler to collect the deposits and scaling which may remain and be circulated in the system after the initial filling.

When the boiler is fixed on the template connect the flue and air ducts (fittings supplied by the manufacturer) according to the instructions given in the following relevant sections.

Connect the condensate outlet to the siphon supplied with the boiler. Connect the siphon to a drain, making sure there is a continuous slope. Horizontal sections must be avoided.

0506_0806

BOILER HEIGHT 950

DRILL HOLES WITH A Ø12 BIT, FIT THE MASONRY

PLUGS AND THE SCREWS PROVIDED

FLUE AXIS

N.B. INCLUDE CONDENSATE DRAIN POINT

 

BOILER WIDTH 600

 

 

gas inlet to the boiler

heating flow

heating return

condensation drain

0602_0701/CG_1469/1

MR: G 1” heating flow

GAS: G 3/4” gas inlet to the boiler

RR: G 1” heating return

SC: condensation drain 22 mm

Figure 5

INSTRUCTIONS PERTAINING TO THE INSTALLER

12

926.772.1 - GB/IE

 

 

Page 12
Image 12
Baxi Potterton WH65, WH46 manual Boiler Installation, Existing system

WH46, WH65 specifications

The Baxi Potterton WH65 and WH46 are renowned for their efficiency and reliability, designed to meet a variety of heating requirements in residential and commercial settings. These models exemplify advanced engineering, ensuring that users benefit from optimal performance and reduced energy consumption.

One of the main features of these units is their exceptional heat output. The WH65 boasts a powerful output of 65 kW, making it suitable for larger properties or commercial spaces with high heating demands. Conversely, the WH46 provides a more moderate output of 46 kW, ideal for smaller applications. Both models are built to provide consistent heating, contributing to a comfortable environment regardless of external weather conditions.

Technologically, the Baxi Potterton WH series utilizes a robust cast iron heat exchanger, renowned for its durability and long lifespan. This feature not only enhances the unit’s efficiency but also aids in better heat retention, allowing the boiler to operate at optimal levels for extended periods. The heat exchanger is complemented by an intelligent control system, which allows for easy adjustments to settings, ensuring that the heating output can be modified to suit specific needs.

Another important characteristic of the WH65 and WH46 is their user-friendly interface. Both models are equipped with clear and intuitive controls, making it easy for homeowners and technicians alike to operate and maintain the units. For added convenience, these boilers can be integrated with external controls, enabling smart temperature management and energy saving.

The efficiency ratings of the WH65 and WH46 models are commendable, allowing for lower energy bills and a reduced carbon footprint. These boilers comply with stringent environmental standards, contributing to eco-friendliness without compromising performance.

In terms of installation, both models are designed with flexibility in mind. They can be installed in various positions, adapting to space constraints or specific installation requirements. Furthermore, the boilers are relatively lightweight for their category, making them easier to handle during the installation process.

In conclusion, the Baxi Potterton WH65 and WH46 are exemplary heating solutions that combine power, efficiency, and user-friendly features. They cater to diverse heating needs while ensuring durability and compliance with modern energy standards, making them a popular choice among consumers and heating professionals alike.