INSTALLATION INSTRUCTIONS for | Form 7516 rev. 0 |
HeatManager™ 2.5 model 7516 (145 PSI max. operating pressure)
LIGHT COMMERCIAL STEAM HEATING SYSTEM ECONOMIZER
Description
The HeatManager™2.5 is a patented microprocessor- controlled
Operation
After installation, setting the switch on the unit to the ‘ON’ position activates the device. The LCD display indicates the various ‘modes’ of the device, and sensed Pressures and Temperatures. The possible messages and their explanation are:
‘STANDBY MODE’ - The boiler is operating under its own internal controls, which have turned the burner off. This occurs for a period of time after the burner has shut down.
‘ECONOMIZER MODE’ - The boiler’s controls have requested the burner to come on but the HeatManager™ has sensed that there is available steam which can be used without burning fuel. The burner will remain off and useful energy will be extracted from the boiler’s existing supply of steam.
‘HEATING MODE’ – The burner is allowed to fire.
‘HEATING LOW LIMIT’ - The unit has switched the burner on due to an increase in load. This condition may occur occasionally. If this message appears frequently, the boiler’s pressure controls are set too low and should be increased in 2 PSI increments until the message stops appearing frequently.
During normal operation, one of the above messages will be alternated with the message(s) below.
‘STEAM PRESS = ‘ - The measured value of the boiler steam pressure is displayed in PSIG.
‘DOM. TEMP = ‘ - The measured value of the domestic hot water outflow temperature is displayed in degrees F. *
*Note: This message will only appear if the boiler supplies domestic hot water and the optional second sensor is installed (see Sensor Section of these instructions).
In the event that a sensor fails, the HEATMANAGER™ will return full control of the burner to the boiler’s controls, the ‘Power/Normal’ indicator will blink, and the following message will be displayed:
‘SENSOR FAILURE ‘
If this message appears, see the instructions under Service and Troubleshooting or call your installer for service.
Installation
The HeatManager™ is electrically installed in series with the boiler pressuretrol as shown in the wiring diagram (Fig. 1a or Fig.1b on the reverse side of this page). Check the shipping box label for correct model. The HEATMANAGER™ can be used with 24, 115 and 220 Volts for power and control.
For safety, power to the boiler must be shut off during installation. For improved savings, it is recommended that the low pressure setting of the boiler’s controls be set no lower than 30 PSI. If the setting is found to be lower, it should be raised to at least 30 PSI .
Positioning
The unit can be mounted in any position. For readability of the display, the vertical position is preferred. Depending on the boiler’s configuration, the unit can be mounted on an electric junction box or directly on an external pressuretrol. Remove a knockout from the junction box or pressuretrol and mount the unit using the standard ½’ electrical fitting on the case, and the supplied
Wiring
All wiring and connections must comply with Local and National Electrical Codes. The unit should be wired as shown in the wiring diagram (Fig. 1a or Fig. 1b) on the reverse side.
NOTE: All unused leads should be trimmed and individually insulated.
Sensors Installation
Attach the pressure sensor to the boiler using standard plumbing practices for the pressures involved. The pressure sensor must be mounted to a ‘steam pigtail siphon tube’ to protect the sensor from high temperatures (see fig. 3). Failure to do so will void the sensor warranty. Route the sensor wire back to the HeatManager™ controller in a workman like manner. Insert the sensor connector into the ‘Steam Pressure Sensor’ jack on the unit.
For boilers that also supply domestic hot water; attach a temperature sensor (as shown in fig. 2) to the domestic hot water
If any of the sensor leads are too short, they can be extended by using HeatManager™ extension cables, or make your own using standard ‘modular telephone’ wire and connectors (see Fig. 4).
Checkout
Recheck wiring one last time and make sure that the sensor(s) is plugged into the proper jack(s). The sensor(s) is only detected during
Service and Troubleshooting
The HeatManager™ doesn’t require any maintenance and will provide years of trouble free operation. The unit may be disconnected at any time by putting the switch to the ‘OFF/BYPASS’ position. In this position, the unit has no effect on the system and the boiler functions as it did prior to the HeatManager™ installation. This allows service personnel to diagnose any boiler problems without the unit intervening.
If at any time the ‘SENSOR FAILURE’ message appears on the front panel display, a sensor is not operating properly and the HeatManager™ has returned full burner control back to the Boilers’ controls. The failed sensor can be identified by turning the HeatManager™ off, then back on, and observing the display to see which connected sensor is not recognized. Replace the unrecognized sensor with a known good one, and repeat the above test. If the sensor still isn’t recognized, there is a problem with the HeatManager™ which should be returned for service.
NOTE: Installer, please leave these instructions with the unit for future reference.