Maintenance and Service

Annual Professional

Service Required

Tampering with or making incorrect adjustments could lead to equipment malfunction and result in asphyxia- tion, explosion or fire.

yDo not tamper with the burner or controls or make any adjustments unless you are a trained and qualified service technician.

yTo ensure continued reliable operation, a qualified service technician must service this burner annually.

yMore frequent service intervals may be required in dusty or adverse environments.

yOperation and adjustment of the burner requires technical training and skillful use of combustion test instruments and other test equipment.

Annual service — by qualified service techni- cian

Have the burner inspected, tested and started at least annually by a qualified service technician. This annual test/inspection should include at least the following:

ˆReplace the oil supply line filter. The line filter cartridge must be replaced to avoid contamination of the fuel unit and nozzle.

ˆInspect the oil supply system. All fittings should be leak- tight. The supply lines should be free of water, sludge and other restrictions.

ˆRemove and clean the pump strainer if applicable.

ˆReplace the nozzle with the exact brand, pattern, gph, flow rate and spray angle.

ˆClean and inspect the electrodes for damage, replacing any that are cracked or chipped.

ˆCheck electrode tip settings. Replace electrodes if tips are rounded.

ˆInspect the igniter spring contacts.

ˆClean the cad cell lens surface, if necessary.

ˆInspect all gaskets. Replace any that are damaged or would fail to seal adequately.

ˆInspect the combustion head and air tube. Remove any car- bon or foreign matter. Replace all damaged units with exact parts.

ˆClean the blower wheel, air inlet, air guide, and burner housing of any lint or foreign material.

ˆIf motor is not permanently lubricated, oil motor with a few drops of SAE 20 nondetergent oil at each oil hole. DO NOT over oil motor. Excessive oiling can cause motor failure.

ˆCheck motor current. The amp draw should not exceed the nameplate rating.

ˆCheck all wiring for secure connections or insulation breaks.

ˆCheck the pump pressure and cutoff function.

ˆCheck primary control safety lockout timing.

ˆCheck ignition system for proper operation.

ˆInspect the vent system and chimney for soot accumulation or other restriction.

ˆClean the appliance thoroughly according to the manufac- turer’s recommendations.

ˆCheck the burner performance. Refer to the section “Set combustion with test instruments”.

ˆIt is good practice to make a record of the service performed and the combustion test results.

Monthly maintenance — by owner

‰Observe combustion air openings and vent system for integrity. Openings must be clean and free of obstructions.

‰Check oil lines and fittings to verify there are no leaks.

‰Observe burner ignition and performance to verify smooth operation.

‰Shut the system down if you observe abnormal or questionable operation. Call a qualified service agency for professional inspection and service.

Form 6104 BCF10-R06

17

Page 17
Image 17
Beckett CF1000 manual Annual Professional Service Required, Monthly maintenance by owner

CF1000 specifications

The Beckett CF1000 is a cutting-edge, reliable, and efficient commercial burner designed for use in various heating applications. Known for its exceptional performance, it is increasingly popular among businesses and contractors looking for an effective solution to meet their heating needs.

One of the main features of the CF1000 is its advanced combustion technology. The burner is engineered to deliver optimal combustion efficiency, reducing emissions and enhancing fuel economy. This technology not only helps in lowering operational costs but also aligns with modern environmental regulations, making the CF1000 a responsible choice for energy-conscious businesses.

Another notable characteristic of the CF1000 is its ability to handle multiple fuel types, including oil and natural gas. This versatility allows users to choose the best fuel source for their specific application, contributing to operational flexibility. Additionally, the CF1000 is equipped with a modulation system that adjusts the burner output in response to demand, ensuring consistent heating without unnecessary energy consumption.

The CF1000 also stands out for its compact design, making it easy to install in various settings, whether in commercial buildings or industrial facilities. Its robust construction is designed to withstand demanding conditions, ensuring longevity and reliability. Moreover, the burner comes with advanced safety features, including flame monitoring and integrated shut-off systems, helping to prevent potential hazards during operation.

Ease of maintenance is another significant advantage of the Beckett CF1000. The design incorporates user-friendly service access points, allowing technicians to perform routine maintenance and inspections quickly and efficiently. This not only ensures optimal performance but also extends the lifespan of the burner.

Furthermore, the CF1000 is supported by Beckett's extensive customer service and technical support. Their commitment to quality and satisfaction means that users can rely on expert assistance whenever needed, ensuring peace of mind.

Overall, the Beckett CF1000 is a premier choice for those seeking a high-performance commercial burner. With its advanced combustion technology, versatile fuel options, compact design, and a wealth of safety features, it delivers reliable heating solutions suitable for a wide range of applications. Its ease of maintenance combined with robust support services makes the CF1000 an intelligent investment for any business prioritizing efficiency, safety, and reliability in their heating systems.