Instruction Manual – Model CF2300A Oil Burner

Verify firing rate

Figure 2 – Air tube mounting dimensions

Refer to appliance manufacturer’s instructions (if avail- able) for firing rate and nozzle selection. Otherwise, the maximum recommended firing rate for the burner depends on the length of the firing chamber and the distance from the burner center to the chamber floor. Verify that the cham- ber dimensions are at least as large as the minimum values given in Figure 1. If the appliance dimensions are smaller than recommended, reduce the firing rate accordingly.

Verify air tube

 

 

 

 

 

 

 

T

 

 

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

F

EInsertion depth

GAir tube to inside of chamber

– 0.25" ± 0.125"

1T Air tube length

DTube diameter

The information in this section may be disregarded if the air tube is supplied by the appliance manufacturer.

Two tube arrangements are available –

Tube KG — 7.0 to 19.9 GPH per

Table 2

Tube KS — 10.0 to 19.9 GPH per

Table 2

Maximum firing capacity depends on the firebox pressure. Use Table 2 to verify the correct air tube type for the firing rate required. Use Tube KS only when Tube KG cannot provide the firing rate required.

See Figure 2 to verify the correct air tube length and air tube combination code.

Figure 1 – Min. combustion chamber dimensions

L

A

2305

Firing rate

 

Minimum dimensions

 

(refractory-lined)

(wet-base boilers)

 

 

A

 

L

A

 

L

5 to 10 gph

8.0"

 

35.0"

8.0"

 

40.0"

10 to 15 gph

9.0"

 

40.0"

9.0"

 

50.0"

15 to 20 gph

11.0"

 

55.0"

11.0"

 

60.0"

E

 

 

 

2304

 

 

 

Install the burner with a 2° pitch as shown.

A.T.C. Codes

(A.T.C. = Air Tube Combination)

 

Tube KG

 

Tube KS

 

 

 

 

 

 

 

 

(Dim T)

(Dim D)

 

(Dim F)

(Dim T)

(Dim D)

 

(Dim F)

 

 

 

 

 

 

 

 

All —

6¹⁄₂”

 

2¹⁵⁄₁₆”

All —

8¹⁄₈”

 

3¹¹⁄₁₆”

 

 

 

 

 

 

 

 

6¾”

CF

66 KG

6¾”

CF

66 KS

 

8¾”

CF

86 KS

 

 

 

 

 

 

10¼”

CF 102 KG

11”

CF 110 KS

13¾”

CF 136 KG

14½”

CF 144 KS

 

 

 

 

 

 

17¾”

CF 176 KG

18½”

CF 184 KS

 

 

 

 

 

 

 

 

Table 2 – Air tube capacity vs. firebox pressure

Firebox

Tube KG

Tube KS

 

 

 

 

pressure

No reserve

10%

No reserve

10%

(In. w.c.)

 

air

turndown

air

turndown

 

 

 

 

 

0.019.9 GPH 19.9 GPH 19.9 GPH 19.9 GPH

0.219.2 GPH 19.1 GPH 19.7 GPH 19.6 GPH

0.418.5 GPH 18.3 GPH 19.5 GPH 19.3 GPH

0.617.9 GPH 17.6 GPH 19.4 GPH 19.1 GPH

0.817.2 GPH 16.8 GPH 19.2 GPH 18.8 GPH

1.016.5 GPH 16.0 GPH 19.0 GPH 18.5 GPH

Note: 10% turndown indicates sufficient reserve air to reduce the CO2 in the flue to 90% of its value.

Note: The above ratings may vary 5% due to variations in actual job conditions.

Form 6104 BCF-23-R0399

5

Page 5
Image 5
Beckett CF 2300A instruction manual Verify firing rate, Verify air tube, Air tube capacity vs. firebox pressure

CF 2300A specifications

The Beckett CF 2300A is a highly regarded oil burner designed for residential and light commercial use. Known for its reliability and efficient performance, the CF 2300A is a favored choice among HVAC professionals and homeowners alike. This model optimizes fuel efficiency while ensuring a consistent and dependable heat output, making it suitable for various heating applications.

One of the standout features of the Beckett CF 2300A is its advanced combustion technology. Equipped with a unique air-to-fuel ratio control system, this burner optimizes the mix of air and fuel, resulting in cleaner combustion and increased energy savings. This technology not only enhances heating efficiency but also reduces the environmental impact by minimizing harmful emissions.

The CF 2300A is designed with a sleek, compact profile that allows for easy installation in tight spaces. Its versatile mounting options and adjustable dimensions accommodate various installation configurations, making it a flexible choice for both new and retrofitting projects. Additionally, the burner is compatible with a wide range of fuel types, including traditional heating oil, which enhances its usability across different heating systems.

Built for durability, the Beckett CF 2300A features robust components that withstand the rigors of daily operation. Its heavy-duty construction ensures longevity, reducing the need for frequent replacements or repairs. Furthermore, it includes a reliable ignition system that provides quick starts and consistent operation, making it a dependable choice for homeowners.

Another key characteristic of the CF 2300A is its low noise operation. The design incorporates noise-reducing technologies that minimize the sound output during operation, contributing to a comfortable indoor environment. This feature is particularly beneficial in residential settings where quiet heating solutions are desired.

In conclusion, the Beckett CF 2300A oil burner combines innovative technologies with reliable performance characteristics. Its advanced combustion system, flexible installation options, robust construction, and quiet operation make it an optimal choice for residential and light commercial heating needs. With a focus on efficiency and longevity, the CF 2300A continues to set a standard in the industry, providing dependable heat while prioritizing environmental sustainability.