Instruction Manual – Model CF2300A Oil Burner

b.Slowly rotate the air adjusting plate (increase the amount of air) as the damper drives to high-fire.

c.Lock down air adjusting plate at the high-fireair set- ting found in Table 5 for the high-firerate.

6.Use combustion test instruments to adjust the burner.

a.Adjust the air until a trace of smoke is achieved with

CO2 level as high as possible (lowest possible O2). Example: 13.5% CO2 (2.5% O2) with a trace of smoke.

b.Increase the air to reduce CO2 by 2 percentage points at a zero smoke level. (Increase O2 by 3 percentage points at a zero smoke level.)

Example: Reduce CO2 from 13.5% to 11.5%, with zero smoke (or increase O2 from 2.5% to 5.5%).

c.A margin of reserve air has been added to accommo- date variable conditions.

7.Check the breech draft pressure against the appliance manufacturer’s recommended setting (typically + 0.1" W.C.).

8.If the breech pressure is higher or lower than recommended level, adjust the appliance breech damper to achieve the

specified setting. Recheck the smoke and CO2 levels. Adjust burner air if necessary.

9.Once all settings are complete and satisfactory, rotate the damper linkage arm (Figure 12, item f) until it touches the damper rod (Figure 12, item d) and tighten the damper linkage arm screw securely.

Set low-fire air

1.Loosen the air adjusting plate (Figure 12, item m) screw and set the air adjusting plate at the low-fireair setting found in Table 5, page 13. The damper should stay at the high-fire setting. The damper linkage will prevent move- ment of the damper plate.

2. Move the low-fire hold switch from the “ OUT” to the “ IN” position.

a.The damper will return to the low-fireair setting.

3.Check the smoke and CO2 (O2) levels.

a.Pull a smoke sample from the flue.

b.The sample should be clean (zero smoke level).

c.Check the CO2 (O2) level:

CO2 should be at 11 to 12% (O2 at 5.9 to 4.5%).

If the CO2 is less than 11% (O2 more than 5.9%), decrease the air and check the smoke level.

4.Operate the burner from low fire to high fire and back to verify operation.

5.Turn the burner off. Wait one or two minutes (for chamber to clear) and then turn on again to verify starting charac- teristics.

6.Perform limit circuit performance test specified by appli- ance manufacturer to verify operation of burner/appli- ance combination.

Maintenance and service

The burner must be serviced at least annually by a qualified service technician to assure continued reliable operation. Operation and adjustment of the burner requires technical knowledge and the use of combustion test instruments. Do not tamper with the burner or controls. Failure to comply could result in failure of the burner or system, resulting in severe personal injury, death or substantial property damage.

Annual service

Inspect combustion air and vent systems.

— by qualified service technician

Replace oil filter.

 

Oil motor (if not permanently lubricated).

Have the burner inspected, tested and started at least annually

 

by a qualified service technician. This annual test/inspection

Monthly maintenance

should include at least the following:

 

— by owner

Replace oil nozzle.

 

Clean burner and blower wheel (if needed to remove lint

Observe combustion air openings and vent system for

or debris).

integrity. Openings must be clean and free of any obstruc-

Test ignition and combustion at low and high fire and

tions.

verify air damper settings.

Check the oil lines and fittings to verify there are no leaks.

Test oil supply line vacuum - verify that it is within al-

Observe burner ignition and performance to verify smooth

lowable range indicated in fuel unit literature.

operation.

Check pump pressure to nozzle at low and high fire.

Shut the system down if you observe abnormal or ques-

Inspect fuel system (including tank, lines and all connec-

tionable operation. Call a qualified service agency for

tions).

professional inspection and service.

Form 6104 BCF-23-R0399

15

Page 15
Image 15
Beckett CF 2300A instruction manual Maintenance and service, Set low-fire air, Annual service, Monthly maintenance

CF 2300A specifications

The Beckett CF 2300A is a highly regarded oil burner designed for residential and light commercial use. Known for its reliability and efficient performance, the CF 2300A is a favored choice among HVAC professionals and homeowners alike. This model optimizes fuel efficiency while ensuring a consistent and dependable heat output, making it suitable for various heating applications.

One of the standout features of the Beckett CF 2300A is its advanced combustion technology. Equipped with a unique air-to-fuel ratio control system, this burner optimizes the mix of air and fuel, resulting in cleaner combustion and increased energy savings. This technology not only enhances heating efficiency but also reduces the environmental impact by minimizing harmful emissions.

The CF 2300A is designed with a sleek, compact profile that allows for easy installation in tight spaces. Its versatile mounting options and adjustable dimensions accommodate various installation configurations, making it a flexible choice for both new and retrofitting projects. Additionally, the burner is compatible with a wide range of fuel types, including traditional heating oil, which enhances its usability across different heating systems.

Built for durability, the Beckett CF 2300A features robust components that withstand the rigors of daily operation. Its heavy-duty construction ensures longevity, reducing the need for frequent replacements or repairs. Furthermore, it includes a reliable ignition system that provides quick starts and consistent operation, making it a dependable choice for homeowners.

Another key characteristic of the CF 2300A is its low noise operation. The design incorporates noise-reducing technologies that minimize the sound output during operation, contributing to a comfortable indoor environment. This feature is particularly beneficial in residential settings where quiet heating solutions are desired.

In conclusion, the Beckett CF 2300A oil burner combines innovative technologies with reliable performance characteristics. Its advanced combustion system, flexible installation options, robust construction, and quiet operation make it an optimal choice for residential and light commercial heating needs. With a focus on efficiency and longevity, the CF 2300A continues to set a standard in the industry, providing dependable heat while prioritizing environmental sustainability.