Section: Start the Burner

Estimating Rate

Manifold to Furnace Pressure information can be used to estimate the burner’s firing rate when it is not possible to clock a meter for the rate.

To estimate the burner’s firing rate:

Measure the furnace pressure over fire

Measure the manifold pressure (at the manifold pressure test connection).

Subtract the furnace pressure from the manifold pressure

Compare the result to the data in Figures 14A, 14B, or 14C as appropriate for your burner.

Clocking a Gas Meter

Before you clock the meter you must make sure that the burner is operating at a steady rate, and that it is the only thing that is using gas that would flow through the meter.

Uncorrected Flow Rate

Locate the dial that moves the fastest and determine how many cubic feet are represented by one revolution of its dial.

Use your watch for timing and observe how many cubic feet are used in one minute.

Multiply by 60

Example: The dial is a one cubic foot dial, and goes around 7 ½ times in one minute. That gives 7.5 cubic feet per minute. Multiply by 60 to get 450 cubic feet per hour (CFH) as your uncorrected flow rate.

Pressure Correction

Gas is compressible, the higher the pressure on it, the smaller the number of cubic feet it occupies. To correct for that you will need to know the gas pressure at the meter.

If there’s a gauge at the meter, read it while the gas is flowing. (If not, measure the gas pressure in the line downstream of the meter before any valves or regulators, with no gas flowing.)

Convert the gas pressure to PSI if you measure it in any other units. (1 PSI = 27.7 inches water column)

Add 14.7 to the meter pressure, divide their sum by 14.7, and multiply that result times the uncorrected flow rate to obtain the pressure corrected flow rate.

Example: The meter in the example above is operating at 14” WC.

14 / 27.7 = 0.5 PSI at the gauge; 14.7 + 0.5 =15.2; 15.2 / 14.7 = 1.034 correction factor;

1.034 x 450 = 465 CFH corrected for pressure

Temperature Correction

Gas volume also changes with the temperature of the gas. Most gas meters are temperature compensated. They say so on the face of the index and don’t require temperature correction. The temperature we correct to is 60° F. That’s close to the temperature of the ground, so usually it’s not necessary to correct for temperature from underground lines.

Measure the gas temperature at the meter.

Add 460 to the gas temperature and divide 520 by the result to obtain the correction factor.

Multiply the pressure corrected flow rate times the temperature correction factor.

Example: The meter in the example is connected to an above ground line on a hot day and shows 100° F gas temperature. 460 + 100 = 560; 520 / 560 = 0.929; 465 x 0.929 = 432 CFH corrected for pressure and temperature. This figure is often called SCFH (for standard cubic feet per hour).

BTU’s and MBH

Natural Gas

The BTU content of natural gas varies from one location to another, and even from day to day at a fixed location. For firing estimates it is usually assumed to be 1000 BTU’s per standard cubic foot.

To calculate BTU/Hr firing rates multiply SCFH times 1000.

Example: 432 SCFH x 1000 = 432,000 BTU/Hr. MBH stands for thousands of BTU’s per hour. Since

1 cubic foot of natural gas contains 1000 BTU, 1 MBH equals 1 SCFH of gas flow.

Example: 432 SCFH = 1,080 MBH

LP (Liquified Petroleum) Gas

The BTU content of LP gas varies with the relative quantities of propane and butane in each delivery of gas and changes as liquid level in the tank falls. For firing estimates it is usually assumed to be 2,500 BTUs per standard cubic foot.

To calculate BTU/Hr firing rates multiply SCFH times 2,500.

Example: 432 SCFH x 2500 = 1,080,000 BTU/Hr. MBH stands for thousands of BTU’s per hour. Since 1 cubic foot of propane gas contains 2,500 BTU, 1 MBH equals 0.4 SCFH of gas flow.

Example: 432 SCFH = 1,080 MBH

24

Page 24
Image 24
Beckett CG50 Estimating Rate, Clocking a Gas Meter, Uncorrected Flow Rate, Pressure Correction, Temperature Correction

CG25, CG50, CG15 specifications

Beckett CG25, CG15, and CG50 are advanced burner systems designed for optimal performance in residential and commercial heating applications. Developed with state-of-the-art technology, each model offers distinct features and characteristics tailored to meet varying demands.

The Beckett CG25 is engineered for medium-output applications, providing reliable heating with exceptional efficiency. One of its standout features is the high-performance combustion head which enhances the air-fuel mixing process, leading to improved burn quality and reduced emissions. Additionally, the CG25 incorporates a fully automatic control system that allows for precise temperature regulation, contributing to energy savings and lower operational costs.

The Beckett CG15, meanwhile, is ideal for smaller residential systems. It stands out for its compact design, making it easy to install in tight spaces. Despite its size, the CG15 does not compromise on performance. It features advanced flame retention technology, which ensures a stable and efficient burn, while its low noise operation adds convenience for users. The CG15 also benefits from a robust safety system that includes a lockout feature to prevent unsafe operation.

On the higher end, the Beckett CG50 is designed for larger heating applications and is capable of generating high outputs while maintaining fuel efficiency. Its innovative design encompasses a three-stage combustion process that enhances efficiency and minimizes emissions significantly. The CG50 also features advanced diagnostic capabilities, providing real-time feedback and enabling proactive maintenance, which increases reliability and prolongs equipment life.

All three models are built with durability in mind, utilizing high-quality materials to withstand harsh operating conditions. They are compatible with various types of fuel, including oil and gas, making them versatile solutions for a broad range of heating needs. Beckett's commitment to sustainability is evident in the design of these burners, as they comply with stringent environmental regulations.

In conclusion, the Beckett CG25, CG15, and CG50 systems represent a blend of innovative technology, efficiency, and robust design. Their unique features cater to different heating demands, making them suitable for various applications while ensuring both performance and reliability. Whether for residential or commercial use, these burners are ideal choices for anyone looking to invest in a high-quality heating solution.