![](/images/new-backgrounds/1029242/2924253x1.webp)
|
|
|
|
| Section: Start the Burner | |
6. High gas pressure switch – With the burner firing | Oxygen – For both low fire and high fire it is | |||||
and a manometer attached to the test port nearest | recommended that you measure the oxygen (O2) early | |||||
the high pressure switch, gradually increase the | in the test sequence because high levels of carbon | |||||
gas pressure until the high pressure switch opens | monoxide can be created at very low or even very high | |||||
O2 levels. The typical operating range is between 2.5% | ||||||
and shuts the burner off. Note the pressure and | ||||||
– 4.5 %. The equivalent carbon dioxide (CO2) operating | ||||||
manually reset the switch. The high gas pressure | range is 9% – 10.5%. | |||||
switch should be set at one and one half times the |
|
| High excess air levels reduce the | |||
high fire manifold pressure (see nameplate data in |
|
| ||||
|
| |||||
|
| flame’s UV output and the scanner | ||||
Figure 1 or set switch as determined by testing). |
|
| ||||
signal that proves the burner is firing. | ||||||
7. | Carbon monoxide (CO) – An operating range of 0 | |||||
manometer attached to the | ||||||
PPM is recommended for the burner. The maximum | ||||||
the burner electrical switch off and observe that | ||||||
carbon monoxide (CO) level permitted in the flue gas by | ||||||
the gas pressure does not increase after several | the UL 795 Standard is 400 PPM (0.04%). | |||||
minutes. This proves total closure of the main gas | Stack Temperature – The stack temperature should be | |||||
valve. | ||||||
8. Flame safeguard safety lockout – Simulate a | within the range specified by the appliance manufacturer. | |||||
It is influenced by input firing rate, flame shape, excess | ||||||
flame failure by turning the main gas supply off. The | air ratio, and cleanliness of boiler flue passages. This | |||||
control should shut the burner off on safety within | temperature, combined with the ambient temperature, | |||||
and O2% (or CO2) is used in calculating the appliance | ||||||
the safety lockout time. | ||||||
efficiency. | ||||||
9. Flame sensor circuit (flame rod) – With the | ||||||
|
|
| ||||
burner power switch turned off, refer to the wiring | Recommended Combustion Test Sequence | |||||
diagram supplied with the control and locate the |
|
|
| |||
sensor connection terminals. Place DC voltmeter | 1. Adjust the draft or breech pressure to the appliance | |||||
probes in the flame amplifier test jacks. With the | manufacturer’s recommended level. | |||||
burner firing, the flame signal should be steady and | 2. Measure the carbon monoxide level and adjust | |||||
at least 1.25 VDC. | ||||||
air settings, if necessary, to regulate it to about 50 | ||||||
10.Flame sensor circuit (UV scanner) – With the | ||||||
PPM for a starting point. | ||||||
burner power switch turned off, refer to the wiring | 3. Measure the O2 or CO2 at the 50 PPM CO level. | |||||
diagram supplied with the control and locate the | ||||||
sensor connection terminals. Place DC voltmeter | For this discussion, assume the O2 is 1.5% (11% | |||||
probes in the flame amplifier test jacks. With the | CO2). | |||||
burner firing, the flame signal should be steady and | 4. Open the air adjustment until the O2 level is | |||||
at least 1.25 VDC. | increased by at least 1% or to 3% O2 (whichever | |||||
|
|
| is higher). This should reduce the CO level and | |||
Use Test Instruments to Set Combustion | provide a margin of reserve air to accommodate | |||||
variable conditions. | ||||||
Verify that all boiler sections, canopy, and access plates | 5. Sample the CO level again. It should be in the 0 to | |||||
20 PPM range. | ||||||
or doors are fully equipped with gaskets and sealed | ||||||
6. Check the draft to ensure it still meets | ||||||
against any leakage, which could affect the combustion | ||||||
test results. Before making these tests, operate the | specifications. If a major change in draft is | |||||
burner for several minutes to allow the heating system | required, repeat the above steps. | |||||
temperature to stabilize or nearly reach | 7. Perform any final adjustments and lock the air | |||||
levels. Record all results in the | settings securely. Run the burner through several | |||||
reference. | cycles to verify prompt ignition and stable burner | |||||
Draft – Set the breech or furnace pressure to the | operation. | |||||
|
|
| ||||
level specified by the appliance manufacturer. Typical |
|
|
| |||
example: +0.10” W. C. |
|
|
| |||
|
| Always use calibrated test |
|
|
| |
|
|
|
|
| ||
|
| instruments to set combustion |
|
|
| |
|
|
|
|
| ||
levels. Verify that test instruments are calibrated and |
|
|
| |||
in good working condition. If not already provided, drill |
|
|
| |||
test access holes in the flue pipe near the breech (or |
|
|
| |||
upstream of the boiler breech damper, if applicable) and |
|
|
| |||
in the front mounting plate area for firebox pressure. Be |
|
|
| |||
careful not to damage any |
|
|
|
CG15, CG25, CG50 Burner Manual
27