Page 6 RWB 6104 BNX R02
Prepare the Burner
General
In most cases, the burner is ready to mount to the
appliance. There can be situations where the burn-
er needs to be recon gured to perform properly in
the appliance. Review the appliance manufactur-
er’s speci cations prior to installing to determine if
any modi cation is required to properly con gure
the burner.
Instruction on how to perform the following burner
preparation tasks can be found in the Professional
Maintenance section.
Remove / install burner nozzle
Check head/air adjusting plate
Low Firing Rate Baf e (If speci ed)
The NX Low Firing Rate Baf e (LFRB), refer to Fig-
ure 2, reduces the burner air ow and pressure. Re-
fer to the appliance manufacturer’s instructions or
the Beckett OEM Speci cation Guide part number
6711. To avoid poor burner performance, do not
omit the baf e when speci ed or install the baf e
when not speci ed.
Note:
The Low Firing Rate Baf e may have been factory
installed. If eld installation is required, insert the
Low Fire Rate Baf e into the housing, aligning the
mounting screw hole with the notched hole in the
burner housing. Make note that the curved end
of the baf e should be below the motor bolt boss.
Tighten the thread cutting screw to 12-24 in-lbs.
Figure 2. – Mounting Low Fire Rate Baf e in burner housing.
SK9698
Inspect/Prepare Installation Site
Figure 3. – Mounting Burner in Appliance
SK9668
Mount Burner on Appliance
Verify that the air tube installed on the burner pro-
vides the correct insertion depth. Refer to Figure
3.
The end of the air tube should normally be 1/4”
back from the inside wall of the combustion cham-
ber. Never allow the leading edge of the retention
ring to extend into the chamber, unless otherwise
speci ed by the appliance manufacturer.
Bolt the burner to the appliance using the factory-
welded ange.
The burner is shipped without the by-pass plug in-
stalled.
Install the by-pass plug in two-pipe oil supply systems
ONLY.

Failure to comply could cause immediate pump

seal failure, pressurized oil leakage and the po-

tential for a re and injury hazard.

Do Not Install By-pass Plug with 1-Pipe System
WARNING
!
Connect Fuel Lines
The oil supply inlet pressure to the burner cannot
exceed 3 psig.
Insure that a pressure limiting device is installed
in accordance with the latest edition of NFPA 31.
Do not install valves in return line.
Gravity Feed Systems: Always install an anit-
siphon valve in the oil supply line or a solenoid
valve (RWB Part # 2182602U) in the pump/noz-
zle discharge tubing to provide backup oil ow
cut-off protection.

Damage to the lter or pump seals could cause

oil leakage and a re hazard.

Oil Supply Pressure Control Required
!
!CAUTION