2Wiring examples

2Wiring examples

Controller name, symbol and allowable number of controllers.

Name

Symbol

Allowable number of controllers

Heat source unit controller

OC

 

BC Controller (main)

BC

One controller for one OC

BC Controller (sub)

BS

Zero, one or two controllers for one OC

Indoor Unit Controller

IC

One to twenty four controllers for one OC

Remote Controller

RC

Maximum of two per group

Example of a group operation system with multiple heat source units (Shielding wires and address setting are necessary.)

<Examples of transmission cable wiring>

[Fig. 10.3.1] M-NET Remote Controller (P.5)

[Fig. 10.3.2] MA Remote Controller (P.5)

<A>

Change the jumper connector from CN41 to CN40.

 

 

 

<B>

SW2-1:ON

 

 

 

 

<C>

Keep the jumper connector on CN41.

 

 

 

A Group 1

B Group 4

C Group 5

D Shielded wire

E Sub remote controller

( )

Address

 

 

 

 

<Wiring Method and Address Settings>

a.Always use shielded wire when making connections between the heat source unit (OC) and the indoor unit (IC), as well for all OC-OC, and IC-IC wiring intervals.

b.Use feed wiring to connect terminals M1 and M2 and the earth terminal on the transmission cable terminal block (TB3) of each heat source unit (OC) to terminals M1, M2 and terminal S on the transmission cable block of the indoor unit (IC).

c.Connect terminals 1 (M1) and 2 (M2) on the transmission cable terminal block of the indoor unit (IC) that has the most recent address within the same group to the terminal block on the remote controller (RC).

d.Connect together terminals M1, M2 and terminal S on the terminal block for central control (TB7) for the heat source unit (OC).

e.On one heat source unit only, change the jumper connector on the control panel from CN41 to CN40.

f.Connect the terminal S on the terminal block for central control (TB7) for the heat source unit (OC) for the unit into which the jumper connector was inserted into CN40 in Step above to the ground terminal [Fig. 10.3.1] M-NET Remote Controller (P.5) in the electrical component box.

g.Set the address setting switch as follows.

*To set the outdoor unit address to 100, the outdoor address setting switch must be set to 50.

Unit

Range

Setting Method

 

 

Use the most recent address within the same group of indoor units. With an R2 system with sub BC controllers, set the

 

 

indoor unit address in the following order:

IC (Main)

01 to 50

1 Indoor units connected to the main BC controller

2 Indoor units connected to BC sub controller 1

 

 

 

 

3 Indoor units connected to BC sub controller 2

 

 

Set the indoor unit addresses so that all the addresses of 1 are smaller than those of 2, and that all the addresses of 2

 

 

are smaller than those of 3.

 

 

 

IC (Sub)

01 to 50

Use an address, other than that of the IC (Main) from among the units within the same group of indoor units. This must be

in sequence with the IC (Main)

 

 

Heat source Unit

51 to 100

Use the most recent address of all the indoor units plus 50

BC controller (Main)

51 to 100

Heat source unit address plus 1. When the set indoor unit address duplicates the address of another indoor unit, set the

new address to a vacant address within the setting range.

 

 

 

 

 

BC controller (Sub)

51 to 100

Lowest address within the indoor units connected to the BC controller (sub) plus 50

 

 

 

M-NET R/C (Main)

101 to 150

Set at an IC (Main) address within the same group plus 100

M-NET R/C (Sub)

151 to 200

Set at an IC (Main) address within the same group plus 150

 

 

 

MA R/C

Unnecessary address setting (Necessary main/sub setting)

 

 

 

h. The group setting operations among the multiple indoor units is done by the remote controller (RC) after the electrical power has been turned on.

<Permissible Lengths>

1M-NET Remote controller

Max length via outdoor units: L1 + L2 + L3 + L4 and L1 + L2 + L3 + L5 and L1 + L2 + L6 = 500 m [1640 ft] (1.25 mm2 [AWG16] or more)

Max transmission cable length: L1 and L3 + L4 and L3 + L5 and L6 and L2 + L6 = 200 m [656 ft] (1.25 mm2 [AWG16] or more)

Remote controller cable length: r1, r2, r3, r4 = 10 m [32 ft] (0.3 to 1.25 mm2 [AWG22 to 16])

If the length exceeds 10 m [32 ft], use a 1.25 mm2 [AWG16] shielded wire. The length of this section (L8) should be included in the calculation of the maximum length and overall length.

2MA Remote controller

Max length via outdoor unit (M-NET cable): L1 + L2 + L3 + L4 and L1 + L2 + L6 = 500 m [1640 ft] (1.25 mm2 [AWG16] or more)

• Max transmission cable length (M-NET cable): L1 and L3 + L4 and L6 and L2 + L6 = 200 m [656 ft] (1.25 mm2 [AWG16] or more)

Remote controller cable length: c1 and c1 + c2 + c3 and c1 + c2 + c3 + c4 = 200 m [656 ft] (0.3 to 1.25 mm2 [AWG22 to 16])

3Transmission booster

Max transmission cable length (M-NET cable): 1 L8 + L1 + L2 + L3 + L5 + L6 = 200 m [656 ft] (1.25 mm2 [AWG16])

2 L8 + L1 + L2 + L3 + L5 + L7 = 200 m [656 ft] (1.25 mm2 [AWG16])

3 L8 + L1 + L2 + L4 = 200 m [656 ft] (1.25 mm2 [AWG16])

4 L6 + L5 + L3 + L4, L4 + L3 + L5 + L7 = 200 m [656 ft] (1.25 mm2 [AWG16])

Remote controller cable length: r1, r2 = 10 m [32 ft] (0.3 to 1.25 mm2 [AWG22 to 16])

If the length exceeds 10 m [32 ft], use 1.25 mm2 [AWG16] shielded cable and calculate the length of that portion (L4 and L7) as within the total extended length and the longest remote length.