Berner International B-24, B-22 manual Troubleshooting, Sympto M S, Cause

Models: B-24 B-22

1 6
Download 6 pages 48.82 Kb
Page 5
Image 5
TROUBLESHOOTING

TROUBLESHOOTING

SYMPTO M S

CAUSE

 

 

 

FAN WON’T START

1)

Selector in “OFF” position

 

 

2)

Check 3-phase line leads for power across all 3 phases

 

 

 

(If one line is dead, check fuses or breaker in main

 

 

 

disconnect)

 

 

3)

Check fuse on control circuit transformer

 

 

4)

Try “SUM” setting. If fan runs, but won’t run on “WIN”,

 

 

 

check 1THS outdoor thermostat (if used) for open R-B

 

 

 

contact; check limit switch on door for open-contact.

 

 

5)

Check overload relay on fan starter. Iftripped,reset. If

 

 

 

relay continues to trip, check motor full load amps versus

 

 

 

M starter’s overload relay’s setting (adjustment dial on the

 

 

 

frontofstarter). See manufacturer’s instruction sheet.

 

 

 

 

FAN

OPERATES, GAS

1)

Selector in “SUM” position. Turn to “WIN”

PILOT WILL NOT IGNITE,

2)

Check wire 6 to ground 115 V (defective selector switch or

GREEN “TURN RESET”

 

wiring to same)

DOES

NOT LIGHT

3)

Check wire 7 to ground (bad 13-14 contactinstarter

 

 

4)

9 to ground (bad R-W contact lo-gas switch)

 

 

5)

10 to ground (bad R-B contact in hi-gas switch)

 

 

6)

11 to ground (bad 4-5 contact in control relay)

 

 

7)

12 to ground (bad C-NO contact in airflow switch; pressure

 

 

 

setting too high, turn adjustment screw CCW until switch

 

 

 

trips; clogged tubing in airstream)

 

 

8)

13 to ground (reset Thermodisc, inside “handy-box”)

 

 

9)

Check toggle switch in mounting base of Fireye (must be

 

 

 

left in “ON” position)

 

 

 

 

FAN

OPERATES, GAS

1)

Defective time delay TDR. (Pull from socket, turn RESET,

PILOT WILL NOT IGNITE,

 

and try again)

GREEN “TURN RESET”

2)

(IRI type only) - One or both gas pressure switched tripped.

LIGHTS CONTINUOUSLY

 

Press reset lever. If low-pressure can’t be reset, check for

WHENEVER FAN RUNS

 

cause of inadequate pressure. Check supply pressure ahead of

 

 

 

regulator, if pressure exceeds rating of regulator,it may pass no gas or

 

 

 

failtoregulate.

 

 

 

 

FAN

OPERATES, GAS

1)

Press reset button on Fireye

PILOT WILL NOT IGNITE,

2)

If Fireye won’t reset, check for presence of continuous gas

GREEN “LOCKOUT”

 

pilot flame

LIGHTS CONTINUOUSLY

 

 

WHENEVER FAN RUNS

 

CAUTION - In this case turn off manual cock in pilot

 

 

 

line before stopping fan. Then investigate cause of

 

 

 

pilot valve 1V sticking open

 

 

3)

If Fireye can be reset, but on next try-for-ignition, “TURN RESET”

 

 

 

lights, refer to next sections. If “LOCKOUT” lightsrefertolast

 

 

 

symptom.

 

 

 

 

5

Page 5
Image 5
Berner International B-24, B-22 manual Troubleshooting, Sympto M S, Cause