CHAPTER 5: Configuration

5.3.4.Callback Security

The Callback function provides an additional layer of security when users attempt to access command mode via modem. When this function is properly configured, modem users will not be granted immediate access to command mode upon entering a valid password; instead, the unit will disconnect, and dial a user-defined number before allowing access via that number. If desired, users may also be required to re- enter the password after the Outlet Managed PDU dials back.

In order for Callback Security to function properly, you must first enable and configure the feature via the System Parameters menu as described in this section, and then define a callback number for each desired user account as described in Section 5.5. To access the Callback Security menu via the Text Interface, type /F and press [Enter] and then select the Callback Security option. To access the Callback Security menu via the Web Browser Interface, place the cursor over the General Parameters link, wait for the flyout menu to appear, and then Click on the "Callback Security" link.

In both the Text Interface and Web Browser Interface, the Callback Security Menu offers the following options:

Callback Enable: This prompt offers five different configuration options for

the Callback Security feature: (Default = On - Callback (Without Password Prompt.)

Off: All Callback Security is disabled.

On - Callback (Without Password Prompt): Callbacks will be performed for user accounts that include a Callback Number, and the login prompt will not be displayed when the user’s modem answers. If the account does not include a Callback Number, that user will be granted immediate access.

On - Callback (With Password Prompt): Callbacks will be performed for user accounts that include a Callback Number, and the login prompt will be displayed when the user’s modem answers (accounts that include a Callback Number will be required to re-enter their username/password when their modem answers.) If the account does not include a Callback Number, then that user will be granted immediate access.

On - Callback ONLY (Without Password Prompt): Callbacks will be performed for user accounts that include a Callback Number, and the username/password prompt will not be displayed when the user’s modem answers. Accounts that do not include a Callback Number will not be able to access command mode via modem.

43

Page 44
Image 44
Black Box MPSH8-D20-208+V, MPSH8-S20-208+V, MPSH16-D20-208+V, Outlet Managed PDU, MPSH16-D20-120V manual Callback Security

MPSH8-S20-120V, MPSH8-D20-120V, Outlet Managed PDU, MPSH8-D20-208+V, MPSH16-D20-120V specifications

The Black Box MPSH Series, specifically the MPSH16-D20-208+V, MPSH8-S20-208+V, MPSH16-D20-120V, and MPSH8-D20-208+V, represents a state-of-the-art solution in the realm of Outlet Managed Power Distribution Units (PDUs). Designed for seamless integration within data centers and server rooms, these PDUs are engineered to support the ever-evolving demands of modern IT infrastructures while ensuring energy efficiency and optimal performance.

One of the hallmark features of the MPSH series is its robust management capabilities. These PDUs allow for individual outlet monitoring and control, enabling IT managers to efficiently manage power consumption across various devices. This granular control helps in identifying underutilized equipment, managing power distribution more effectively, and ultimately lowering operational costs.

In terms of connectivity, the MPSH units are equipped with multiple outlets—providing flexibility to connect numerous devices. The MPSH16-D20-208+V, for instance, features sixteen outlets, while the MPSH8 series boasts eight. This variety allows for customization based on specific needs in different settings, whether it is a small server room or a large data center.

The MPSH PDUs also incorporate advanced technologies to enhance power efficiency and reliability. They are equipped with features such as surge protection, which shields sensitive equipment from voltage spikes, and power factor correction, which optimizes energy usage for improved efficiency. Additionally, remote management capabilities enable IT personnel to access power metrics and control outlet status from any location via a secure web interface, providing enhanced visibility and proactive management of power flows.

Safety and compliance are paramount in the design of the MPSH series. These PDUs adhere to industry standards, ensuring that they meet the necessary regulations for quality and safety, which is critical in preventing downtime and electrical hazards.

Moreover, the installation process for MPSH PDUs is straightforward, facilitating quick deployment within existing infrastructures. Their compact design allows for mounting in various configurations, maximizing space efficiency in crowded server racks.

Overall, the Black Box MPSH16-D20-208+V, MPSH8-S20-208+V, MPSH16-D20-120V, and MPSH8-D20-208+V Outlet Managed PDUs deliver a blend of functionality, efficiency, and safety, making them an indispensable asset for organizations looking to optimize their power management strategies in today’s data-driven environment.