SPECIFICATIONS Leave ample room for servicing when the water heater is installed – do not block access to the burner, inspec- tion door, handholes or controls. Leave room to pipe the unit and connect the fuel and electricity.
BURNER SPECIFICATIONS
Bock Multi- |
| |||||||||||
Flue Series |
|
|
|
|
|
|
|
|
|
|
|
|
Nominal Storage | 176 gal. |
| 168 gal. | 160 gal. | 221 gal. | 212 gal. | 204 gal. | 192 gal. | 273 gal. | 260 gal. | 251 gal. | 242 gal. |
Stack Size, in. | 8 in. |
| 8 in. | 10 in. | 8 in. | 8 in. | 10 in. | 12 in. | 10 in. | 12 in. | 14 in. | 14 in. |
Turboflues, Qt. | 3 |
| 5 | 7 | 3 | 5 | 7 | 10 | 7 | 10 | 12 | 14 |
Anode Rods, Qt. | 4 |
| 4 | 6 | 4 | 4 | 6 | 10 | 6 | 8 | 10 | 11 |
|
|
|
|
|
|
|
|
|
|
|
|
|
Bock Oil |
| |||||||||||
Fired Model |
|
|
|
|
|
|
|
|
|
|
|
|
Max. Fire Rate | 3.0 gph |
| 4.5 gph | 6.0 gph | 3.2 gph | 4.6 gph | 6.1 gph | 8.2 gph | 6.0 gph | 7.1 gph | 9.0gph | 11.0 gph |
Btu/hr input | 400000 |
| 600000 | 800000 | 450000 | 650000 | 850000 | 1150000 | 800000 | 1000000 | “1,250,000” | 1500000 |
Burner Make | Wayne |
| Wayne | Wayne | Wayne | Wayne | Wayne | Wayne | Wayne | Wayne | Wayne | PowerFlame |
Model | EH |
| EH | EH | EH | EH | EH | FH | EH | FH | FH | |
Nozzle | 3.0 x 80A |
| 4.5 x 80B | 5.5 x 80A | 3.0 x 80B | 4.5 x 80B | 6.0 x 70B | 6.0 x 70B | 6.00x70B* | |||
OEM Number |
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Burner Make | Carlin |
| Carlin | Carlin | Carlin | Carlin | Carlin |
| Carlin |
|
|
|
Model | 201 CRD |
| 301 CRD | 301 CRD | 201 CRD | 301 CRD | 301 CRD |
| 301 CRD |
|
|
|
Nozzle | 2.5 x 70B* |
| 4.0 x 80B* | 5.0 x 80A or 70W* | 2.5 x 70B* | 4.0 x 80B* | 5.0 x 80A or 70W* |
| 5.0 x 80A or 70W* |
|
|
|
OEM Number | 9828500B361E |
| 9859400B | 9859400B | 9828500B361E | 9859400B | 9859400B |
| 9859400B |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Bock Dual |
| |||||||||||
Fuel Model |
|
|
|
|
|
|
|
|
|
|
|
|
Max. Fire Rate | 3.0 gph |
| 4.5 gph | 6.0 gph | 3.2 gph | 4.6 gph | 6.1 gph | 8.2 gph | 6.0 gph | 7.1 gph | 9.0 gph | 11.0 gph |
Btu/hr input | 400000 |
| 600000 | 800000 | 450000 | 650000 | 850000 | 1150000 | 800000 | 1000000 | 1,250,000 | 1500000 |
Burner Make | Power Flame |
| Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame |
Model |
| |||||||||||
Nozzle | 1.65x70B* |
| 2.50x70B* | 3.25x70B* | 1.75x80B* | 2.50x70B* | 3.5x70B* | 4.50x70B* | 3.25x70B* | 4.0x70B* | 5.00x70B* | 6.00x70B* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Bock Power |
| |||||||||||
Gas Model |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Btu/hr input | 400000 |
| 600000 | 800000 | 450000 | 650000 | 850000 | 1150000 | 800000 | 1000000 | “1,250,000” | 1500000 |
Burner Make | Power Flame |
| Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame | Power Flame |
Model |
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
Burner Controls: |
|
|
|
|
|
|
|
|
|
| ||
| Burner | Primary Control | Detector |
|
|
|
| |||||
| Wayne EH |
| R8184G 1294 |
| C554A |
|
|
|
| |||
| PF |
| RM7895C 1012 | C7072A |
|
|
|
| ||||
| PF | RM7895C 1012 | C7072A |
|
|
|
| |||||
CARLIN 201CCRD, 301CRD | P/N 4020002 | C1440700K |
|
|
|
|
Aquastats: High Limit Honeywell Model L4080 & Averaging Control Model L8100C.
Flue Tubes:
Flue tubes constructed of steel minimum, 1/8 in. thick, 6 in. OD by 35 in. long, and provided with fins welded in a spiral pattern.
Model | Number of Flues |
3 | |
3 | |
5 | |
5 | |
7 | |
7 | |
10 | |
12 | |
14 |